Azbil CY8100C1000 Specifications & Instructions

Azbil CY8100C1000 Specifications & Instructions

Insertion type co2 concentration transmitter

Advertisement

Insertion Type CO
Part No. 83165722-002 (Assembly Kit)
General
Model CY8100C in combination with Part No. 83165722-002
is an insert type CO
concentration transmitter used for
2
detecting concentration of carbon dioxide (CO
This product can be used in a wide range of applications
such as monitoring of CO
2
the control of outdoor air intake.
Features
Non-dispersive infrared absorption method (NDIR)
Linear output signal in 1-5 V DC range
Long-term stability
Model Number and Part Number
For the insertion type CO
concentration transmitter, both of
2
the following items are required.
Model/Part number
CY8100C1000
Main unit
83165722-002
Assembly kit
- Sampling probe
- Gasket, 2 screws, 2 washers
- Cable assembly
Specifications
Item
Measuring range
0 to 2000 ppm CO
Operating principle
Non-dispersive
method (NDIR)
± (50 ppm + 5 % of reading)
Measuring accuracy
Continuously ON: ±150 ppm/year
Drift
Continuously OFF (reference value):
±15 ppm/48 hours at 50 %RH
Time constant
15 min. or less (windless)
3 min. or less (0.6 m/s wind)
Environmental
Operation CO
conditions
Temperature: 0 to 50 °C
Humidity: 0 to 95 %RH (non-condensing)
Transport/
Temperature: -20 to 50 °C
Storage
Humidity: 0 to 95 %RH (in moisture-
proof package)
24 V AC ± 10 %, 50 to 60 Hz
Power supply voltage
Power consumption
Max. 3 VA
Output signal
1 to 5 V DC (linear with 0-2000 ppm
CO
Allowable load resistance
5 kΩ or more
Wiring
Power supply: 2-wire
CO
2
Model CY8100C1000 (Main Unit)
) in ducts.
2
concentration in return ducts and
Description
Specification
Concentration
2
infrared
absorption
concentration: 0 to 2000 ppm
2
concentration)
2
concentration output: 2-wire
2
Concentration Transmitter
Optional Parts
Part number
83165722-002
83104511-001
83104981-001
(1/2)
Item
Initial stabilizing time
Allowable vibration
Insulation resistance
Enclosure rating (main unit) IEC IP65 (dust-proof and water-proof)
Weight
Material
Application
1
Specifications/Instructions
Description
Assembly kit (for replacement)
- Sampling probe
- Gasket, 2 screws, 2 washers
- Cable assembly
Zero calibration service bag
(CO
zero calibration gas generator)
2
Zero calibration service cylinder
(CO
zero calibration gas cylinder)
2
Specification
Continuously OFF for 48 hours or longer:
Approx. 10 days (∗ Product in a
package is exceptional.)
Other than the above: Approx. 3 days
2
4.9 m/s
(10 to 150 Hz)
100 MΩ or higher at 500 V DC
(between the case and each lead wire)
Approx. 350 g
Main unit
- Case: PC + ABS plastic
®
(Bayblend
FR90)
®
- Cover: PC Makrolon
6555
Sampling probe: PC Makrolon
Indoor duct, chamber
AB-6256
(2/2)
®
6555

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CY8100C1000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Azbil CY8100C1000

  • Page 1 AB-6256 Specifications/Instructions Insertion Type CO Concentration Transmitter Model CY8100C1000 (Main Unit) Part No. 83165722-002 (Assembly Kit) General Model CY8100C in combination with Part No. 83165722-002 is an insert type CO concentration transmitter used for detecting concentration of carbon dioxide (CO ) in ducts.
  • Page 2: Safety Instructions

    This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil Corporation’s sales representative.
  • Page 3: Assembly Kit

    AB-6256 Dimensions Main unit (with sampling probe assembled to) Main unit Sampling probe Cable (1 m long) 4P connector Figure 1. Dimensions of the main unit with sampling probe (mm) Assembly kit • Sampling probe shows the mounting orientation. Mounting hole (on the duct) φ4 φ4...
  • Page 4: Precautions For Installation

    AB-6256 Installation Precautions for installation • Installation environment Although the main unit enclosure conforms to IEC IP65 for dustproof and waterproof, avoid installing in locations exposed to corrosive atmosphere or direct sunlight. • Handling of the main unit The main unit is packaged in a tightly sealed aluminum moisture-proof bag for shipment. This prevents large output drift that may be caused from moisture absorption of the main unit continuously non-energized.
  • Page 5: Installation Of Main Unit

    AB-6256 Cable assembly: Following is an example of cable assembly installation using round outlet box (JIS* C8340) with two entries. ∗ JIS: Japanese Industrial Standard Lead the controller cable into the outlet box through an entry. Connect the controller cable with the cable assembly, as shown in Fig.
  • Page 6: Wires Connection

    AB-6256 Wires Connection Connection of power supply line IMPORTANT: Do not apply power supply voltage other than 24 V AC. Otherwise, it may damage the product. Use insulation transformer. Do not share the 24 V AC power supply with any other device. If the transformer is shared, a loop will formed at common and the product may get damaged.
  • Page 7: Maintenance

    AB-6256 Maintenance Periodic inspection Since the measurement gases flow into the inside of the housing, annual cleaning of circuit boards inside the housing is recommended. Periodic calibration The output drift (a maximum of 150 ppm/year) occurs even if this product is in continuously energized state. Be sure to conduct a CO zero gas calibration every year.
  • Page 8 Note that the yellow LED also lights up during: • Pressing a button • Calibration Specifications are subject to change without notice. Building Systems Company http://www.azbil.com/ Rev. 1.0 Jul. 2012 AB-6256 Y (W03) (J: AI-6256 Rev. 1.6) Printed in Japan.