INM F809F-Plus (DTM) Rev 1.8
The wizard is executed in 3 steps:
•
Step 1: select the fieldbus segment power supply
Select the model of fieldbus power supply in use. If you are using a model other
than listed in the wizard, choose 'Custom limits configuration' and enter the limits
according to the datasheet of the fieldbus power supply in use.
Default values are as shown in the following table:
The following limits will be set for the respective selected power supply:
Selected Fieldbus
Power supply
F101
F102
F6xx Series (FPS-IPM)
F801
F802
918 *.* 1
918 *.* 2
Note that the limit values have to be in rising sequence at all times:
Low-low-limit ≤ low-limit < high-limit ≤ high-high-limit
and high limit must be at least 1 V higher than low limit.
In case the calculated values are not in sequence with the low-low-limit and high-
high-limit stored in the F809F , the wizard will reject the calculated values and keep
the old values without notification to the user.
Associated
Low-limit
21.3 V
27.7 V
24.8 V
21.3 V
27.8 V
27.8 V
18.5 V
Associated
High-limit
24.2 V
30.2 V
30.2 V
24.2 V
30.2 V
30.2 V
22.5 V