3. High temperature and overload protection (E8)(AP1 below means control board of outdoor unit)
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
ambient temperature is higher
If the radiating of indoor
and outdoor unit is good?
If the indoor and outdoor
fan are running normally?
Replace outdoor
mainboard
Installation and Maintenance
E8 is displayed
If the outdoor
than 53℃?
No
No
Yes
End
Normal protection, please
use it after improving the
Yes
outdoor ambient temperature
No
Improve the radiating environment
of unit (clean the heat exchanger
Yes
and remove surrounding obstacles)
No
Connect normally?
Yes
Fan capacitor is broken?
No
Motor is broken?
No
Replace mainboard
Unit restarts
Yes
normally
Unit restarts
Yes
normally
Adjust the
Yes
connection
Replace Fan
Yes
capacitor
Replace Motor