Regency Panorama PG121NG1-R Owners & Installation Manual page 18

Table of Contents

Advertisement

INSTALLATION
Vertical Flueing with Two (2) 90
Option
V
A)
1' (305mm) Minimum
B)
2' (610mm) Minimum
C)
3' (914mm) Minimum
D)
4' (1.22m) Minimum
E)
5' (1.5m) Minimum
F)
6' (1.86m) Minimum
With the above options, maximum total pipe length if 37 feet with
minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 9
18
Elbows
o
H
4' (1.22m) Maximum
6' (1.86m) Maximum
9' (2.7m) Maximum
12' (3.6m) Maximum
15' (4.5m) Maximum
17' (5.1m) Maximum
elbows is required.
o
Vertical Flueing with Three (3) 90
Option
A)
B)
C)
D)
With the above options, maximum total pipe length if 37 feet with
minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 11
Vertical Flueing with Two (2) 90
Option
V
A)
1' (305mm) Minimum
B)
2' (610mm) Minimum
C)
3' (914mm) Minimum
D)
4' (1.22m) Minimum
With the above options, maximum total pipe length if 37 feet with
minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 10
Elbows
o
V + V1
2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max.
3' (914mm) Min. 4' (1.22m) Max.
4' (1.22mm) Min. 6' (1.86m) Max.
5' (1.5m) Min.
8' (2.4m) Max.
Regency PG121/PG131 Zero Clearance Room Sealed Gas Fireplace
Elbows
o
H + H1
2' (610mm) Maximum
4' (1.22m) Maximum
6' (1.86m) Maximum
8' (2.4m) Maximum
elbows is required.
o
H
H + H1
5' (1.5m) Max.
8' (2.4m) Max.
12' (3.6m) Max.
elbows is required.
o