Electrical Panel; Safety Components - Riello RS 1300/E C01 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Voltage on the QRI cell
Minimum value for correct operation: 3.5V DC (value on AZL dis-
play at about 50%).
If the value is lower, it could be due to:
cell not positioned correctly
low voltage (lower than 187V)
bad regulation of the burner
In order to measure, use a voltmeter with a 10V DC scale con-
nected as in the diagram (Fig. 34).
Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistance Service in order to carry out the necessary adjustments.
EN 676
Theoretical max CO
2
GAS
0 % O
2
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
7.2.4

Electrical panel

Turn off the burner's power supply using the main
system switch.
DANGER
In the event of maintenance/replacement of components in the
lower part of the electrical panel, access is possible via the front
of the panel itself, following the directions below:
 unscrew the screws 2) of the control panel 1)(Fig. 35);
 extract the control panel 1) and turn it 90°, hooking it with the
brackets 3) in the profile of the electrical panel as shown in
Fig. 35;
 after performing the operation, install the control panel 1) in
the electrical panel with the appropriate screws 2), arranging
the cables present.
Failure to install the control panel 1) in the seat of
the electrical panel, results in the machine's loss
of "IP" protection.
WARNING
Air excess
Max. output.
Max. output.
  1.2
  1.3
CO
% Calibration
2
 = 1.2
 = 1.3
9.7
9
9.5
8.8
11.6
10.7
11.4
10.5
Maintenance
D9174
2
1
CO
mg/kWh
 100
20094732
 100
 100
 100
Tab. N
7.2.5

Safety components

The safety components should be replaced at the end of their life
cycle indicated in the following table.
The specified life cycles do not refer to the warranty terms indi-
cated in the delivery or payment conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic)(if present)
Flexible hoses (if present)
Fan impeller
31
GB
LMV...
X10-02 / 6
X10-02 / 4
X10-02 / 2
+
0...10 V
Ri > 10 M
Fig. 34
3
1
Fig. 35
Life cycle
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
15 years
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years or 250.000
operation cycles
10 years
5 years or 30.000
pressurised cycles
10 years or 500.000 start-ups
Tab. O