Mitsubishi Electric Mr.Slim PUZ-SM100VKA Service Manual page 77

Hide thumbs Also See for Mr.Slim PUZ-SM100VKA:
Table of Contents

Advertisement

SW2 setting
Discharge temperature (TH4)
−20 to 217
ON
1
2 3 4 5 6
Output step of outdoor FAN
ON
0 to 16
1
2 3 4 5 6
The number of ON / OFF times of com-
pressor
0 to 9999
ON
1
2 3 4 5 6
Compressor integrating operation times
0 to 9999
ON
1
2 3 4 5 6
Compressor operating current
ON
0 to 50
1
2 3 4 5 6
Compressor operating frequency
0 to 255
ON
1
2 3 4 5 6
Error postponement code history (1)
of outdoor unit
ON
1
2 3 4 5 6
Operation mode on error occurring
ON
1
2 3 4 5 6
OCH708
Display detail
77
The black square ( ) indicates a switch position.
Explanation for display
−20 to 217
(When the discharge thermistor detects 100 : or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105 :;
0.5 s
0 to 16
0 to 9999
(When the number of times is 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 42500 times (425 ×100 times);
0.5 s
0 to 9999
(When it is 100 hours or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 2450 hours (245 ×10 hours);
0.5 s
0 to 50
Note: Omit the figures after the decimal fractions.
0 to 9999
(When it is 100 Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125 Hz;
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
Operation mode of when operation stops due to
error is displayed by setting SW2 like below.
(SW2)
ON
1
2 3 4 5 6
0.5 s
2 s
1
05
100 times
0.5 s
2 s
4
25
0.5 s
2 s
2
45
0.5 s
0.5 s
2 s
12
50
Unit
:
Step
10 hours
A
0.1 Hz
Code
display
Code
display