9-3-6. Self-diagnosis <Wireless remote controller>
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
CHECK
CHECK
display
TEMP
ON/OFF
ON/OFF
button
AUTO STOP
FAN
AUTO START
MODE
VANE
CHECK LOUVER
CHECK
TEST RUN
button
SET
RESET
CLOCK
OCH708
[Procedure]
Refrigerant
1. Press the CHECK button twice.
address
display
• "CHECK" lights, and refrigerant address "00" blinks.
• Check that the remote controller's display has stopped before
continuing.
Temperature
2. Press the TEMP
button
• Select the refrigerant address of the indoor unit for the self-diagnosis.
Note: Set refrigerant address using the outdoor unit's DIP switch (SW1).
(For more information, see the outdoor unit installation manual.)
3. Point the remote controller at the sensor on the indoor unit and press
the HOUR button.
HOUR
button
• If an air conditioner error occurs, the indoor unit's sensor emits an
h
intermittent buzzer sound, the operation light blinks, and the check
code is output.
min
(It takes 3 seconds at most for check code to appear.)
4. Point the remote controller at the sensor on the indoor unit and press
the ON/OFF button.
• The check mode is cancelled.
buttons.