Mitsubishi Electric Mr.Slim PUZ-SM100VKA Service Manual page 60

Hide thumbs Also See for Mr.Slim PUZ-SM100VKA:
Table of Contents

Advertisement

9-6. HOW TO CHECK THE PARTS
PUZ-SM100VKA.TH
PUZ-SM125VKA.TH
PUZ-SM140VKA.TH
Parts name
Thermistor(TH3)
Disconnect the connector then measure the resistance with a tester.
<Liquid>
(At the ambient temperature 10°C to 30°C)
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
TH4, TH33
<2-phase pipe>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heatsink>
Thermistor (TH33)
<Comp. surface>
Fan motor(MF1,MF2)
Refer to the next page.
Solenoid valve coil
Measure the resistance between the terminals with a tester.
(At the ambient temperature −10°C to 40°C)
<4-way valve>
(21S4)
Motor for compressor
Measure the resistance between the terminals with a tester.
(Winding temperature 20°C)
(MC)
U
V
W
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
(LEV-A/LEV-B)
(Winding temperature 20°C)
GY
M
1
OG
2
RD
3
YE
4
BK
5
OCH708
PUZ-SM100YKA.TH
PUZ-SM125YKA.TH
PUZ-SM140YKA.TH
Normal
160 kΩ–410 kΩ
TH3
TH6
4.3 kΩ–9.6 kΩ
TH7
TH8
39 kΩ–105kΩ
1190 to 1780 Ω
Refer to "4-2. COMPRESSOR TECHNICAL DATA".
Gray–Black
Gray–Red
Checkpoints
Abnormal
Open or short
Normal
Normal
Normal
Gray–Yellow
Gray–Orange
46 ± 3 Ω
60
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents