When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall
hole, in which the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable
making a loop.
When connecting the cable before installing the indoor unit
Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then
tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and
tightened.
After the cable connection, never fail to fasten the connected cable with the
wiring cover.
Note:
When connecting the cable, con rm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, proper operation can not
be car r i ed out and w i l l cause def ect .
Connecting wiring
1. If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar quali ed person. The type of connecting wire is
H07RN-F.
2. If the fuse on PC board is broken please change it with the type of
T.3.15A/250VAC (Indoor).
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into xed wiring. The breaker should be
all-pole switch and the distance between its two contacts should be not less
than 3mm.
Power Source Installation
The power source must be exclusively used for air conditioner.
In the case of installing an air conditioner in a moist place, please install
rth leakage breaker.
an ea
For installation in other places, use a circuit breaker as far as possible.
Cutting and Flaring Work of Piping
Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the are nut, aring work is carried out.
Flare tool for R410A
Clutch-type
clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A
0~0.5mm
1.0~1.5mm
Flare tooling die
3.Insert the are nut
13
Indoor unit
To Outdoor unit
2
4G1.0mm
Conventional are tool
1.5~2.0mm
1.Cut pipe
2.Remove burs
4.Flare pipe
C
r o
e r
t c
Lean
Damage of are
On Drainage
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.
It becomes
The end is imm-
It waves.
high midway.
ersed in water.
Please pour water in the drain pan of the indoor unit, and
is carried out surely to outdoor.
drainage
In case that the attached drain hose is in a room, please apply heat
insulation to
it without fail.
On Drainage
Code
Trouble description
indication
Room temperature
E1
sensor failure
Heat-exchange
E2
sensor failure
Indoor EEPROM
E4
error
Communication
fault between
E7
indo or and outdoor
units
Indoor fan motor
E14
malfunction
Check for Installation and Test Run
Please kindly explain to our customers how to
operate through the instruction manual.
Check Items for Test Run
Put check mark
Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of indoor and outdoor rmly
inserted to the terminal block?
Is the connecting wiring of indoor and outdoor rmly xed?
Is drainage securely carried out?
Is the earth line securely connected?
Is the indoor unit securely xed?
Is power source voltage abided by the code?
Is there any noise?
Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?
Is the operation of room temperature regulator normal?
I
c n
r o
e r
t c
Partial
Too outside
Crack
Less than
5cm
The gap with the
There is the bad
ground is too small.
smell from a ditch
con rm that
Analyze and diagnose
Faulty connector connection;
Faulty thermistor;
Faulty PCB;
Faulty EEPROM data;
Faulty EEPROM;
Faulty PCB;
Indoor unit- outdoor unit signal
transmission error due to wiring
error;
Faulty PCB;
Operation halt due to breaking
of wire inside the fan motor;
Operation halt due to breaking
of the fan motor lead wires;
Detection error due to faulty
indo or unit PCB;