Rebus Beacon Setup - Generac Power Systems PWRcell X7602 Installation Manual

Hide thumbs Also See for PWRcell X7602:
Table of Contents

Advertisement

PWRcell 2P Inv
Enable
Enable
Mod. Settings
Calibrate CTs
Cancel
RCPn: 00010003XXXX
< EXIT
SCROLL > NEXT • SELECT
Figure 6-9. Enabling Inverter (3 of 4)
6. See
Figure
6-10.
create voltage at the DC terminals and begin com-
municating over REbus.
NOTE: Per UL 1741, the PWRcell inverter may require
five minutes upon recovery from a grid outage or island-
ing event before exporting power.
PWRcell 2P Inv.
Inverter
grid connected
AC Power:
AC Voltage:
E-total:
Figure 6-10. Inverter Enabled (4 of 4)
7. Enable all other REbus devices connected to the
system by repeating steps 1-5 for each device. For
further
commissioning
devices, see their respective installation manuals.

REbus Beacon Setup

REbus Beacon allows the PWRcell system to manage
energy production and storage over the course of the
day. This is called Time of Use (TOU) energy manage-
ment. To take advantage of this functionality, the PWR-
cell system must include a PWRcell battery and a reliable
connection to the Internet via an Ethernet connection to a
router.
NOTE: Enabling and setup of the REbus Beacon is only
required when utilized for TOU scheduling. Otherwise, do
not enable the REbus Beacon.
Configuring and Running a TOU Schedule
1. See
Figure
6-11. Navigate to the Beacon device
page and press the center button to enter the
device menu.
Installation Manual for Generac PWRCell Inverter
Menu
Confirm
010012
The inverter is enabled. It will
-02
-36W
248V
2.4Wh
010013
instruction
for
REbus Beacon
TOU Scheduler
disabled
To enable scheduler,
press center button
and select "Enable".
Figure 6-11. Configuring TOU Schedule (1 of 4)
2. See
Figure
highlight Mod. Settings and press the center button
to enter the settings menu.
REbus Beacon
Enable
Mod. Settings
Remove Device
RCPn: 00010003XXXX
< EXIT
Figure 6-12. Configuring TOU Schedule (2 of 4)
3. See
Figure
highlight Access Code and press the center button
to select.
4. Use the up and down arrows to set the Access
Code to 57, and press the center button.
REbus
NOTE: The access code is valid for five minutes. After
five minutes, the access code must be entered again to
enable changes.
Access Code:
TOU Schedule:
Time Zone:
Cancel
Figure 6-13. Configuring TOU Schedule (3 of 4)
5. Use the up and down arrows to highlight TOU
Schedule and press the center button to select.
6. Use the up and down arrows to adjust the TOU
Schedule. Once the desired value is set, press the
center button to exit edit mode.
Commissioning and Setup
6-12. Use the up and down arrows to
SCROLL > NEXT • SELECT
6-13. Use the up and down arrows to
Save
010109
Menu
010110
57
1
4
010111
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pwrcell x11402Pwrcell apke00013

Table of Contents