Reliable F1FR56 QREC Series Quick Start Manual

Reliable F1FR56 QREC Series Quick Start Manual

Quick response extended coverage spray
Hide thumbs Also See for F1FR56 QREC Series:

Advertisement

A complete line of UL Listed and FM Approved
quick response extended coverage sprinklers
for light hazard applications.
Horizontal Sidewall Sprinklers are approved
for installation 4" to 12" (102mm - 305mm)
Model F1FR56 QREC Sprinkler Types
Pendent
Horizontal Sidewall EC-8
Model F1FR56 QREC Recessed Sprinkler Types
Recessed Extended Coverage Pendent F1/F2/FP
Recessed Extended coverage Horizontal Sidewall
Model F1FR56 QREC Concealed
Extended Coverage Pendent
Approval Organizations
1.
Listed by Underwriters Laboratories, Inc. and
Certified for Canada (cULus)
2.
Factory Mutual Approvals (FM)
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Extended Coverage Sprinkler (VNIV)
Product Description
Reliable Models F1FR56 QREC and F1FR56 QREC Re-
cessed Sprinklers are quick response sprinklers which
combine the durability for a standard sprinkler with the at-
tractive low profile of a decorative sprinkler.
The Models F1FR56 QREC and F1FR56 QREC Recessed
Automatic Sprinklers utilize a 3.0mm frangible glass bulb.
These sprinklers have demonstrated response times in
laboratory tests which are five times faster than standard
response sprinklers. This quick response enables these
sprinklers to apply water to a fire much faster than stan-
dard sprinklers of the same temperature rating.
Model F1FR56 QREC Quick Response Extended Cover-
age Concealed Sprinkler is an attractive, low profile con-
cealed sprinkler assembly. This sprinkler assembly uti-
lizes a Model F1FR56 QREC pendent sprinkler in a Model
CCP cup and push-on thread-off cover plate assembly.
The cup is securely factory threaded on the sprinkler's in-
let end. The assembly is shipped with a protective cap.
The sprinkler and cup are easily installed into the sprinkler
fitting using the Model RC1 Sprinkler Wrench. The cover
plate assembly is attached to the sprinkler cup using a
flexible tooth threaded engagement. The cover plate is
attached to the skirt using 135°F (57°C) ordinary tempera-
ture classification solder.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model F1FR56 QREC Series
Quick Response
Extended Coverage Spray
Extended Coverage
Pendent
Extended Coverage
Pendent Concealed
When the ceiling temperature rises, the solder holding
the cover plate melts, allowing the release of this part and
thus exposing the Model F1FR56 QREC sprinkler inside to
the rising ambient temperature.
The Temperature rating of the sprinkler identified by the
color of the glass bulb.
The glass bulb consists of an accurately controlled
amount of special fluid hermetically sealed inside a pre-
cisely manufactured glass capsule. This glass bulb is spe-
cially constructed to provide fast thermal response.
Application
Quick response sprinklers are used in fixed fire protection
systems: Wet, Dry, Deluge or Preaction. Care must be exer-
cised that the orifice size, temperature rating, deflector style
and sprinkler type are in accordance with the latest published
standards of the National Fire Protection Association or the ap-
proving authority having jurisdiction. Quick response sprinklers
are intended for installation as specified in NFPA 13.
Bulletin 028
Rev.
Recessed Extended
Coverage Pendent F1/F2
Extended Coverage
Horizontal Sidewall EC-8
Recessed Extended
Coverage Horizontal
Sidewall EC-8
B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the F1FR56 QREC Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Reliable F1FR56 QREC Series

  • Page 1 135°F (57°C) ordinary tempera- proving authority having jurisdiction. Quick response sprinklers ture classification solder. are intended for installation as specified in NFPA 13. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523...
  • Page 2: Installation Data

    Model F1FR56 Quick Response Extended Coverage Pendent Sprinkler Defl ector: EC Installation Wrench: Model D Sprinkler Wrench Approval Type: Quick Response Extended Coverage - Light Hazard Occupancy Installation Data: Temperature Sprinkler “K” Factor Nominal Thread Sprinkler Approval Rating Identifi cation Orifi...
  • Page 3 Model F1FR56 Quick Response Extended Coverage Horizontal Sidewall Sprinkler Defl ector: EC-8 Installation Wrench: Model D Sprinkler Wrench Approval Type: Quick Response Extended Coverage-Light Hazard Occupancy Installation Data: “K” Factor Sprinkler Nominal Thread Sprinkler Approval Temperature Identifi cation Orifi ce Size Length Organizations...
  • Page 4: Technical Data

    Model F1FR56 Quick Response Extended Coverage Concealed Pendent Sprinkler Installation Wrench: Model RC1 Sprinkler Wrench Approval Type: Quick Response Extended Coverage - Light Hazard Occupancy Technical Data: “K” Factor Sprinkler Nominal Thread Approval Identifi cation Metric Orifi ce Size Organizations Number (SIN) 1/2”...
  • Page 5: Maintenance

    Escutcheon Data: After a 2 (67mm) inch diameter hole is cut in the ceil- Face of Fitting Escutcheon “A” ing, the sprinkler is easily installed with the Model RC1 Adjustment to Ceiling Model Dimension Wall Dimension Wrench. When installing a sprinkler, the protective cap Max Recessed ”...
  • Page 6 Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

Table of Contents