Expansion IO Serial Bus
CIPer 30 expansion IO uses dedicated RS-485 2-wire non-isolated serial bus to communicate with CIPer 30
Controller.

Terminal Blocks

The CIPer 30 Expansion IO uses removable terminal blocks to simplify field wiring of power and cabling. If desired,
you can remove the terminal blocks from the unit, terminate cable, and reset the block when you finish.
To terminate cable:
1. Strip a wire jacket from the end of the cable.
2. Use a small screwdriver to turn the adjustment screw fully counter-clockwise. The clamps in the wire slot
separate as you turn the screw.
3. When the clamps in the wire slot are fully open, insert the stripped end of the cable (the insulation end must
be flush with the terminal block). Be sure to insert all cable strands into the wire slot.
4. Hold the cable in place and turn the adjustment screw clockwise to tighten it until the clamps in the wire
slot secure the cable. Tug gently on the cable to ensure that it's securely terminated
5. Both Expansion I/O modules WEB-O3022H and WEB-O9056H can be connected directly to the WEB-
C3036EPVBNH controller as shown in Fig. 2.
CIPer
MODEL 30 EXPANSION IO MODULES - INSTALLATION INSTRUCTIONS
TM
Figure 3: Stacked CIPer Model 30 controllers with EXPIO modules
7
31-00319-02