Function Of Terminal 50; Function Of Terminal 51; Function Of Terminal 65 - Honeywell Krom Schroder BCU 580 Technical Information

Burner control unit
Table of Contents

Advertisement

Parameters
10 .10 Functions of terminals 50, 51, 65, 66, 67
and 68
The BCU is informed via terminal 50 by a separate au-
tomation system that purging is currently being per-
formed.
Terminals 51, 65, 66, 67 and 68 can each be assigned a
logical AND gating with one of the inputs for the safety
functions (terminals 46 – 50) using an appropriate pa-
rameter. If AND gating is required, the input concerned
can be enabled.
Terminal 51 can also be used as a feedback input for
the maximum capacity position when operated with
IC 40/RBW.

10 .10 .1 Function of terminal 50

Parameter 68
The BCU..F1, F2 or F3 supports centrally-controlled
pre-purge or post-purge. In the case of multiple burner
applications, burners with mechanical combustion air
supply are used. The air for combustion and pre-venti-
lation is supplied by a central fan controlled by a sepa-
rate automation system. The automation system sends
a signal to terminal 50 during purging. At this point, the
BCU opens the air actuator (actuator, air valve) regard-
less of the status of the other inputs. The display shows
P 0 .
Parameter 68 = 23: purge with Low signal.
Parameter 68 = 24: purge with High signal.
BCU 580 · Edition 11.15l

10 .10 .2 Function of terminal 51

Parameter 69
Parameter 69 = 0: Off.
Parameter 69 = 8: AND with input at terminal 46 (emer-
gency stop).
Parameter 69 = 13: Max. capacity position feedback
(IC 40/RBW), see page 81 (Parameter 40 = 3: with
RBW.).

10 .10 .3 Function of terminal 65

Parameter 70
Parameter 70 = 0: Off.
Parameter 70 = 8: AND with input at terminal 46 (emer-
gency stop).
100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents