LonWorks Bus I/O Modules
GENERAL
The CentraLine L
W
Bus I/O Modules communicate
ON
ORKS
via the L
W
Bus.
ON
ORKS
These pluggable CentraLine L
consist of a terminal socket and a removable electronic
module, allowing the socket to be mounted and wired before
the electronic module is installed. All such electronic modules
can be swapped out without disrupting the power and bus
connections: Simply unplug the "old" and insert the "new"
module.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
Disconnect the power supply before you start to install
the control system. More than one disconnect switch may
be required to de-energize the system.
Do not reconnect the power supply until you have
completed the installation.
Unused terminals must be closed (by completely
screwing in the terminal screws), thus preventing the
accidental touching of "live" parts.
Software updates, configuration, and commissioning are all
done automatically by the controller for all L
Modules.
The L
W
Bus I/O Modules may be used with any CPU
ON
ORKS
supporting L
W
Bus communication (e.g., the LION,
ON
ORKS
EAGLE, etc.).
Copyright © 2019 Honeywell GmbH ● All Rights Reserved
W
Bus I/O modules
ON
ORKS
W
Bus I/O
ON
ORKS
Product Data
FEATURES
 Plug-and-play functionality for easy maintenance.
 Pluggable L
W
Bus I/O modules can be exchanged
ON
ORKS
without rewiring. Further, the separate installation of
terminal sockets and electronic modules lower risk of
damage and theft in the construction phase.
 Fast wiring with state-of-the-art push-in terminals (screw-
type terminals also available) and bridge connectors.
 Wide range of sensors supported (NTC20kΩ, NTC10kΩ,
PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000,
Balco500, 0/2...10 V, 0/4...20 mA).
 Binary input LEDs of the CentraLine L
Modules can be configured for status display (off / yellow)
or alarm display (green / red) per channel.
 Configurable safety position for outputs, in case of loss of
communication with the controller.
 Max. wiring flexibility due to optional accessories like
auxiliary terminals and cross-connectors.
 Can be mounted in small installation housings
 Flexible mix of L
W
ON
ORKS
your application requirements.
W
Bus I/O
ON
ORKS
Bus I/O modules covering all
EN0Z-0980GE51 R0119

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell CentraLine CLIOL822A

  • Page 1 L Bus I/O ORKS Modules. The L Bus I/O Modules may be used with any CPU ORKS supporting L Bus communication (e.g., the LION, ORKS EAGLE, etc.). Copyright © 2019 Honeywell GmbH ● All Rights Reserved EN0Z-0980GE51 R0119...
  • Page 2 LONWORKS BUS I/O MODULES – PRODUCT DATA OVERVIEW pluggable pluggable pluggable pluggable ANALOG INPUT ANALOG OUTPUT BINARY INPUT RELAY OUTPUT CLIOLR822A CLIOLR824A LonWorks BUS MODULES CLIOL821A CLIOL822A CLIOL823A CLIOL824A LonWorks Bus XS821-22 XS823 XS824-25 CONTROLLER XSU821-22 XSU823 XSU824-25 Fig. 1. Overview of CentraLine LonWorks Bus I/O Modules Table 1.
  • Page 3 LONWORKS BUS I/O MODULES – PRODUCT DATA Table 3. Pluggable LonWorks Bus I/O Module specifications Analog Input Analog Output Binary Input Relay Output Module CLIOL821A CLIOL822A, CLIOLR822A CLIOL823A CLIOL824A, CLIOLR824A no. of I/Os 8 analog inputs 8 analog outputs 12 binary inputs 6 relay outputs requiring a gold contact or open collector...
  • Page 4: General Features

    8:ABCDFERTAQWESDERT8 72 COM b 24V~ 74 24V 0 Table 4. System constraints 1 2 3 4 5 6 7 8 9 10 11 12 Honeywell Honeywell Max. no. of I/O modules (any depends upon controller type combination) per controller AI/AO Max.
  • Page 5: Analog Input Module

    LONWORKS BUS I/O MODULES – PRODUCT DATA Analog Input Module 10 VDC 24.9 kOHM 199.9 kOHM (8.9 VDC IF CONNECTION INTERRUPTED) Fig. 6. Analog input impedance setpoint (input circuit for NTC10kΩ, NTC20kΩ, wall module setpoint) Fig. 3. CLIOL821A LonWorks Bus AI Module (shown with terminal socket) AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 Legend...
  • Page 6: Cliol821A Analog Input Module

    LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL821A ANALOG INPUT MODULE AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 CLIOL... SHIELD INTERNALLY CONNECTED TO DIN RAIL GND GND GND GND OPT. AUX. TERMINAL MODULE XS814 A1 A2 A3 A4 A5 A6 A7 B1 B (24 VAC) EXTERNAL...
  • Page 7 LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL821A ANALOG INPUT MODULE AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 CLIOL... CLIOL... SHIELD INTERNALLY CONNECTED TO DIN RAIL GND GND GND GND EXTERNAL EXTERNAL 499 OHM DC POWER RESISTOR WITH SUPPLY TWIN WIRE-END FERRULES REQUIRED.
  • Page 8: Analog Output Modules

    LONWORKS BUS I/O MODULES – PRODUCT DATA Analog Output Modules They are installed with the XS821-22 or XSU821-22 Terminal Socket. NC NC AO2 AO3 AO4 AO5 AO6 AO7 AO8 GND GND GND GND GND GND GND GND GND GND 25 26 Fig.
  • Page 9 LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL822A ANALOG OUTPUT MODULE NC NC AO1AO2AO3AO4AO5AO6AO7AO8 CLIOL... 2 3 4 5 6 7 8 SHIELD INTERNALLY CONNECTED TO DIN RAIL GND GND GND GND GND GND GND GND 11 12 13 14 15 16 17 18 OPT.
  • Page 10 LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL822A ANALOG OUTPUT MODULE NC NC AO1AO2AO3AO4AO5AO6AO7AO8 CLIOL... 2 3 4 5 6 7 8 SHIELD INTERNALLY CONNECTED TO DIN RAIL GND GND GND GND GND GND GND GND 11 12 13 14 15 16 17 18 OPT.
  • Page 11 LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL822A ANALOG OUTPUT MODULE NC NC AO1AO2AO3AO4AO5AO6AO7AO8 CLIOL... 2 3 4 5 6 7 8 SHIELD INTERNALLY CONNECTED TO DIN RAIL GND GND GND GND GND GND GND GND 11 12 13 14 15 16 17 18 OPT.
  • Page 12: Binary Input Module

    LONWORKS BUS I/O MODULES – PRODUCT DATA Binary Input Module 18 VDC (NOT STABILIZED) 10 kOHM 150 kOHM DRY CONTACT 4 ... 40 VDC = OPEN 0 ... 2 VDC = CLOSED FAST TOTALIZER Fig. 16. Configuration of a binary input as a fast totalizer Fig.
  • Page 13: Cliol823A Binary Input Module

    LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL823A BINARY INPUT MODULE BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11BI12 8 9 10 11 12 CLIOL... SHIELD INTERNALLY CONNECTED TO DIN RAIL GND GND GND GND GND GND GND GND GND GND 18 19 20 21 22 23 24 DRY CONTACT TOTALIZER...
  • Page 14: Relay Output Modules

    LONWORKS BUS I/O MODULES – PRODUCT DATA Relay Output Modules RELAY BLOCK 1 RELAY BLOCK 2 REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED) Fig. 20. CentraLine L Bus Relay Output Modules ORKS (schematic) Features Fig. 19. CLIOLR824A L Bus Relay Output ORKS Cross-Connecter Module (shown with terminal socket) 1 yellow LED per output Optional versions with manual override switches (Auto, 0,...
  • Page 15 LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL824A RELAY OUTPUT MODULE CLIOL... SHIELD INTERNALLY CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED TO DIN RAIL OPTIONAL AUX. TERMINAL PACKAGE XS814 A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7 FIELD DEVICE FIELD DEVICE POWER SUPPLY...
  • Page 16 LONWORKS BUS I/O MODULES – PRODUCT DATA CLIOL824A RELAY OUTPUT MODULE CLIOL... SHIELD INTERNALLY CROSS CONNECTOR XS815 (FACTORY-MOUNTED) CONNECTED TO DIN RAIL OPTIONAL AUX. TERMINAL PACKAGE XS814 A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7 FIELD DEVICE FIELD DEVICE FIELD DEVICE...
  • Page 17 LONWORKS BUS I/O MODULES – PRODUCT DATA Approvals, Certifications, and Standards Approvals and Certifications  CE-approved  Conforms to EN 60730-1 and EN 60730-2-9  Investigated according to United States Standard UL916 (USL-listed) as well as according to Canadian National Standard(s) C22.2 (CNL-listed) Classification according to EN60730-1 Environmental conditions: For use in home (residential,...
  • Page 18: Screw-Type Terminals

    Fig. 23. CentraLine LonWorks Bus I/O Modules (example shows Manual Overrides), incl. Terminal Socket, outside dimensions (in mm) Manufactured for and on behalf of the Connected Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative: CentraLine Honeywell GmbH Böblinger Strasse 17...