3.7.1 RS-485 Connection
3.7.1 RS-485 Connection
The pin definition for the RS-485 terminal block is shown in Table 3-7.
- Pins 1 and 2 provide a 12VDC / 0.5A bus for use with accessories.
- Pins 3 and 5 are both connected to the DATA+ input.
- Pins 4 and 6 are both connected to the DATA - input.
These connections allow easy daisy-chaining of multiple inverters.
A 120ohm bus termination resistor and associated control switch are located
on the communication board (Table 3-8).
Different RS-485 connection scenarios require different set up for the 120ohm
bus termination resistor.
• When several inverters are cascaded (i.e., "daisy-chained") only the last inverter
in the chain must have its bus termination resistor switched ON (Figure 3-22).
• The length of RS-485 cable is recommended to be less than 30m in general.
- In order to have good transfer quality, twisted-pair wire is recommended to be
used as communication cable.
Pin
1
2
GND (It is NOT the PE)
3
4
5
6
When the RS-485 cable needs to be grounded, please follow the steps below.
1. strip a wire from the shielding layer and properly insulate it
2. crimp the insulated wire to the Y-type lug and fix it in position A
shielding layer
strip from shielding layer
(cross-section: 0.5~1.5 mm²)
ATTENTION
Table 3-7: RS-485 Terminal block wiring
Function
VCC (+12V)
DATA+
DATA-
DATA+
DATA-
INFORMATION
Insulation Tape
1 2 3 4 5 6
VCC GND D+
SNYBL1-4
* Screw torque: 0.59 N•m
43
Installation
D-
D+
D-
A