Applicable Controls - Toshiba RAV-RM301SDT-E Installation Manual

Hide thumbs Also See for RAV-RM301SDT-E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
9

Applicable controls

• For using the wired remote controller RBC-AMS55E*,
refer to the Owner's Manual attached to the wired
remote controller.
REQUIREMENT
• When you use this air conditioner for the first time, it takes
approx. 5 minutes until the remote controller becomes
available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes approx. 5 minutes until the remote controller
becomes available.
Approx. 5 minutes
Power
"SETTING"
"SETTING"
on
flashes
goes out
<When power is turned on for the second (or later)
time>
It takes approx. 1 minute until the remote controller
becomes available.
Approx. 1 minutes
"SETTING"
"SETTING"
Power
on
flashes
goes out
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the settings.
* The settings cannot be changed using the wireless
remote controller, sub remote controller, or remote-
controllerless system (for central remote controller
only). Therefore, install the wired remote controller to
change the settings.
115-EN
 Basic procedure for changing
settings
Change the settings while the air conditioner is not working.
(Be sure to stop the air conditioner before making settings.)
4
Remote
controller
6
is available
1
5
2
1
Push
button and temp. setup
simultaneously for at least 4 seconds or more.
Remote
controller
After a while, the display flashes as shown in the figure.
is available
Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push
the display content, and repeat the procedure from
the beginning.
(No operation of the remote controller is accepted for
a while after
button is pushed.)
(* Display content varies with
the indoor unit model.)
2
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs. You can confirm
the indoor unit for which you want to change
settings.
3
Using temp. setup
/
buttons, specify
CODE No. [
].
4
Using timer time
/
buttons, select
SET DATA [
].
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat from
2
.
• To change other settings of the selected indoor unit,
3
repeat from
.
Use
button to clear the settings.
To make settings after
2
from
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, "SETTING" flashes and
1
then the display content disappears and the air
3
conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
 External static pressure
button
settings
Be sure to set up a tap change based upon the resistance
button to erase
(external static pressure) of the duct to be connected.
To set up a tap change, follow to the basic operation
1
2
3
procedure (
[5d]
• Specify
to the CODE No. in
• For the setup data of
static pressure to be set up from the following table.
<Change on wired remote controller>
Setup data [5d]
0000
0001
0003
0006
The list above is when SW501-1 and SW501-2 is OFF.
* Except standard filter pressure loss.
– 58 –
◆ When wireless remote controller
is used
The settings can be changed with the switch on the indoor
P.C. board.
button was pushed, repeat
SW501-1
OFF
OFF
ON
OFF
ON
4
5
6
).
* Except standard filter pressure loss.
3
.
** When setting the external static pressure to 10 Pa, set
4
, select a setup data of the external
SW501-1 and SW501-2 to OFF, connect a separately sold
wired remote controller, and then set the data of CODE No.
[5d] to "0000" in "External static pressure settings" on this
page.
External static pressure
◆ To restore the factory default
10 Pa*
20 Pa*
To return the DIP switch settings to the factory defaults, set
SW501-1 and SW501-2 to OFF, connect a separately sold
30 Pa* (Factory default)
wired remote controller, and then set the data of CODE No.
50 Pa*
[5d] to "0003" in "External static pressure settings" on this
page.
SW501-1
SW501-2
MCU(IC501)
External static
SW501-2
Setup data
pressure
30 Pa*
OFF
0003
(Factory default)
OFF
0000**
10 Pa*
OFF
0001
20 Pa*
ON
0003
30 Pa*
ON
0006
50 Pa*
116-EN