Internal System Faults - Viessmann VITOCROSSAL CRU 800 kW Service Instructions Manual

Gas condensing boiler
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Displayed fault
System characteristics
code
F F1
Burner control unit in a fault
state; system cools down.
F F2
Burner control unit in a fault
state; system cools down.
F FB
Burner does not start.

Internal system faults

Internal system faults will be shown if the correct pro-
gram sequence can no longer be guaranteed.
Displayed fault
System characteristics
code
F E5, F EC,
Fault in burner control unit
F ED, F FF
area
F FD
Fault in burner control unit
area
Detailed error codes for F FD
Detailed er-
Component/signal Cause of fault
ror code
30
Reset button
31
Fuel valve 2 feed-
back
32
Air pressure switch
1
34
Gas pressure
switch 1
42
Cause
Flue gas temperature lim-
iter has responded
Flue gas temperature
too high
Excessive gas through-
put
Boiler water temperature
limiter has responded.
Boiler water temperature
too high.
Combustion chamber
pressure too high
(LDW2)
Condensate backed up
Flue gas path blocked
Flue gas damper does
not open or close.
Burner control unit con-
figured incorrectly
Cause
Internal system fault and
EMC
See the following table
Programming unit faulty
Wiring
Incorrect return voltage
(e.g. DC voltage)
Actuator faulty
High switching se-
quence, switch flutters
External voltage
High switching se-
quence, switch flutters
External voltage
Measures
Wait until temperature falls below
the permissible flue gas tempera-
ture.
Check the system pressure.
Check heat exchanger surfaces
for soiling.
Reset the burner control unit.
Check the CO
Adjust gas throughput in accord-
ance with the rated boiler heating
output. See "Specification" for
connected values.
Wait until temperature falls below
the permissible boiler water tem-
perature.
Reset the burner control unit.
Check condensate drain and flue
gas path for blockages.
Check flue gas damper.
Check motorised flue gas damp-
er operating parameters.
Measures
Reset the burner control unit. Re-
place the burner control unit if the
fault persists.
See the following table
Measure
Replace programming unit.
Check wiring.
Remove plug from fuel valve 2, reset burner con-
trol unit and check error messages. If F Fd recurs,
replace burner control unit. Otherwise, replace
fuel valve 2.
Check flue gas path and combustion. Check set-
ting LDW1. Check burner gauze assembly for
soiling.
Check the gas supply. Check setting GDW1 and
gas train intake screen.
setting.