Conversion to LPG P

B
A
Fig. 4
1. Turn adjusting screw
A
terfly of the gas train fully towards "
turns towards "+".
2. Insert the coding card for P gas into the burner
control unit. See the following chapter.
Note
Coding card must be ordered separately.
3. Adjust gas pressure switch
To 40 mbar for a nominal supply pressure (flow
pressure) of 50 mbar
To 25 mbar for a nominal supply pressure (flow
pressure) of 37 mbar
on the main volume but-
." Turn back 4
to a new value:
B
Commissioning, inspection, maintenance
4. Start the burner.
5. Measure the CO
content in the flue gas and
2
adjust. See page 16.