6.
6. DMV - D 507/11 - 525/11 DMV-
DLE 507/11 - 525/11 Main flow
setting only possible at V1! Set main
volume on open valve. Set valve
V1 during operation.Check setting
values continuously. Smallest setting
volume flow:
9. Replacing the solenoid Versions
with adjusting plate DMV-D 5.../11or
hydraulic brake DMV-DLE 5../11
1.
Remove hydraulic brake or
adjusting plate as described
on page 6: "Replacing the
hydraulic brake or adjusting
disk", steps 1 - 5.
2.
Replace solenoid
Important: Make sure that the
solenoid no. and voltage are
correct!
3.
Remount hydraulic brake or
adjust-ing plate as described
on page 6. "Replacing the
hydraulic brake or adjusting
plate", steps 7 -11.
7.
7. DMV-DLE Rapid stroke
adjustment V start Factory setting
DMV-DLE: Rapid stroke not adjusted
1.
Unscrew the adjustment cap E
from the hydraulic brake.
2.
Turn the adjustment cap and
use as a tool.
3.
Turn a-clockwise = increase
rapid stroke (+).
8.
8. Replacing hydraulic brake unit or
adjustment plate
1.
Switch off firing system.
2.
Remove locking varnish from
countersunk screw A.
3.
Unscrew countersunkscrew A.
4.
Unscrew socket headscrew B.
5.
Raise adjustment plate C or
hy-draulic brake D.
6.
Remove sealing plug E
7.
Exchange adjustment plate C
or hydraulic brake D
8.
Screw in countersunk and
socket head screw. Only
tighten socket head screw so
that hydraulic brake can just
be turned.
9.
Coat countersunk screw A
with locking varnish.
10.
Leakage test: Pressure tap at
sealing plug 2:
DMV 507-520/11 Pressure tap
at sealing plug 3: DMV 525/11
9.
p max. = 500 mbar.
11.
Perform functional test.
12.
Switch on firing system.
Bentone