Installing
Place the stove on a noncombustible floor or UL
approved floor protector that extends 6 inches to the
front, 6 inches to the sides and 1 inch to the rear of the
stove pipe.
Place the stove away from combustible walls at
least as far as shown in Figures 6, 7 and 8. Please note
the difference in side wall clearance with and without
side shields.
Note that the clearances shown are minimum for
safety but do not leave much room for access when clean-
ing or servicing. Please take this into account when plac-
ing the stove.
Connect the power cord to a 120 V.A.C. 60Hz
grounded receptacle.
Checking Draft
Connect a draft meter to the draft port located on
the lower left rear of the firebox. With a fire burning in
the stove, check the draft with the temperature dial set
at "1" and at "Turbo". The draft reading should never be
less than .03. If the draft is below .03 the chimney must
be improved or a draft inducer must be installed.
WARNING!
If draft is at .00, carbon monoxide
may escape into the room. Too much
carbon monoxide can kill you.
Fig.5
10 1/2"
With or Without Side
Shields
Fig. 6
1"
6"
6"
FLOOR PROTECTOR
Fig. 7
FLOOR PROTECTOR
Fig. 8
7
10 1/2"
5"
6"
8"
16"