FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for a series of problems that could cause a
failure to start or the poor operation of the burner. A fault in the operation usually switches on the lockout lamp,
situated inside the reset button of the control box (7, fig. 1, page 1). When lock-out lamp lights the burner will
attempt to light only after pushing the reset button. After this if the burner functions correctly, the lock-out can
be attributed to a temporary fault. However, if lockout continues, you must determine the cause of the problem
and take the action illustrated in the tables below .
START-UP PROBLEMS
FAULTS
The burner does not
start when the limit
thermostat closes.
Burner runs normally in
the prepurge and igni-
tion cycle and locks out
after 5 seconds ca.
Burner starts with an ig-
nition delay.
The burner locks out,
after the pre-purge pe-
riod,
because
flame does not ignite.
20013751
POSSIBLE CAUSES
Lack of electrical supply.
Gas is not supplied.
The gas pressure switch does not
close the contact.
The connections in the control box
are wrongly inserted.
The
air
pressure
changed over to the operational
position.
The air damper opening motor is
faulty.
The phase-neutral connection is in-
verted
The wiring to the earth is lacking or
ineffective.
Ionisation probe has a ground fault
or is not in contact with flame, or
there is a break in its wiring to con-
trol box, or there is a ground fault
due to its insulation being defective.
Ignition electrode is wrongly
positioned.
Air output is too high.
Valve brake not open enough with
insufficient gas allowed through.
The solenoid valves let too little
gas through.
The valves are faulty.
the
The electric ignition arc is irregular
or not present;
Air in the piping.
Check for voltage at L1-N terminals in 7-
pin plug.
Check the conditions of the fuses.
Check that safety thermostat is not lock
out.
Check gate opening.
Make sure that valves have changed
over to open position and that there are
no short circuits.
Adjust it.
Check and connect completely all the
plugs.
switch
has
Replace the pressure switch.
Check the connection or replace the mo-
tor.
Swap them over.
Make earth connection efficient.
Check right position and, if necessary,
adjust as indicated herein.
Restore electrical connection.
Replace faulty lead.
Adjust properly as indicated herein.
Set the air output according to the
instructions of this manual.
Set correctly.
Check mains pressure and/or adjust the
solenoid valve as indicated in this manu-
al.
Replace them.
Make sure connectors are inserted prop-
erly.
Make sure electrode is in the right posi-
tion as indicated herein.
Completely bleed the gas feed line.
14
GB
SOLUTION