Download Print this page

Galvin Engineering GalvinSafe 190.80.10.90 Product Installation Manualline

Free standing combi shower, axion msr eye/face wash, hand & foot act

Advertisement

Quick Links

®
GalvinSafe
MSR Eye/Face Wash, Hand & Foot Act (HAWS)
PRODUCT CODE:
Galvin Engineering: 190.80.10.90
HAWS: 8330-A + SP220SS
PRE - INSTALLATION
LOCATION OF UNIT: The Model 190.80.10.90 (8330-A) Stainless Steel combination
Shower Eye/Face Wash should be installed in close proximity to potential accident
areas. It should be clearly identified, free from obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4" BSPT with 210 – 600 kPa
flowing pressure. Where sediment or mineral content is a problem, an inlet filter is
recommended.
PLUMBING CONNECTIONS: Inlet supply is male 1-1/4" BSPT. Waste outlet is male 1-
1/4" BSPT.
Free Standing Combi Shower, Axion
th
Version 3.1, 13
Aug. 2021, Page 1 of 7
®

Advertisement

loading

Summary of Contents for Galvin Engineering GalvinSafe 190.80.10.90

  • Page 1 GalvinSafe Free Standing Combi Shower, Axion MSR Eye/Face Wash, Hand & Foot Act (HAWS) PRODUCT CODE: Galvin Engineering: 190.80.10.90 HAWS: 8330-A + SP220SS PRE - INSTALLATION LOCATION OF UNIT: The Model 190.80.10.90 (8330-A) Stainless Steel combination Shower Eye/Face Wash should be installed in close proximity to potential accident areas.
  • Page 2: Parts Breakdown

    STRIPE TAPE* 190.95.90.90 EMERGENCY EYE & SHOWER SAFETY SIGN 190.92.22.20 BOWL 190.91.22.12 FOOT TREADLE 190.91.80.33 TEST TAG L-STRAINER* SS DUST COVER ASSEMBLY* (OPTIONAL) * spare parts will require special order or may not be available (contact Galvin engineering for more details).
  • Page 3: Installation Procedure

    Version 3.1, 13 Aug. 2021, Page 3 of 7 INSTALLATION PROCEDURE Refer to Installation Drawing for clarification. Check parts list to ensure all required parts are included. Use an AS 4020 approved pipe joint sealant on all connections. STEP 1: Prepare the emergency shower foundation by using the floor flange as a template.
  • Page 4 Version 3.1, 13 Aug. 2021, Page 4 of 7...
  • Page 5 Version 3.1, 13 Aug. 2021, Page 5 of 7...
  • Page 6: Troubleshooting

    Version 3.1, 13 Aug. 2021, Page 6 of 7 TROUBLESHOOTING PROBLEM REPAIR CHECKLIST 1. No Flow. Check the main shut-off valve. Verify minimum 210 kPa flowing supply 2. Insufficient water flow. line pressure. 3. a. Verify minimum 210 kPa flowing supply line pressure b.
  • Page 7: Warranty

    April 2021, Page 7 of 7 The warranty set forth herein is given expressly and is the only warranty given by the Galvin Engineering Pty Ltd. With respect to the product, Galvin Engineering Pty Ltd makes no other warranties, express or implied.