Mounting Information; Panel Mount; Panel Cutout Dimensions - Emerson GFK-3072D Quick Start Manual

Rxi – panel pc
Table of Contents

Advertisement

Mounting Information

Panel Mount

The RXi Panel PC can be panel-mounted as presented in the section entitled Mounting to Modular Display.
A Type 4, Type 4X, or IP 66 rating is achieved when mounted to the flat surface of a sufficiently rated enclosure. Please follow
the instructions in the section entitled Installation Steps.
Panel Thickness: 16
1
to 7 gauge (1.6 to 5 mm)
Panel Thickness: 1.6 to 5mm
All measurements within ±0.5mm

Panel Cutout Dimensions

Figure 5: Panel Cutout Dimensions
1
For IP66 installations of 12-inch displays (IC758CSW12SCREEN-A and IC758COW12SCREENSLR-A) use a 14 to 7 gauge (2 to 5 mm) thick panel.
9
Display Size (in)
7
10
12
15
19
24
All panel cutout measurements should be within ±0.5 mm.
Values presented are width and height only.
RXi – Panel PC Quick Start Guide
Width
Width (mm)
Height (mm)
183.5
128.5
255.5
174
317
214.5
398
245.5
482
297
581
360
GFK-3072D