Download Print this page

olympia electronics Power Light Series Quick Start Quide page 2

For non maintained emergency luminaires

Advertisement

3. Connect the new battery with the same type (step 3 of the
installation procedure) and place it in the position of the old one.
4. Follow the step 5 of the installation procedure and power the
device..
total amount of the line's power load.
3. It is sugested to check every month the indication LED for
battery charging, and by pushing instantly the TEST button to
check the emergency cirquit and the lamps. If the luminaire does
not light
contact the installer.
4. It is sugested to check every 6 months the minimum
autononous duration by disconnecting the mains power supply.
Count the time that the lamps light and in case of less time than
the minimum autonomous duration the batteries must be
replaced. If the measured time is considerably less than the
minimum autonomous duration
replacement of the battery and the light source must be done
using parts of the same type, by the manufacturer or by a
competent person.
5.
In case of inactive use for a period greater than 2 months,
disconnect the battery by pulling out the battery's connector.
6. I s not allowed to discard batteries in to common trash
t i
bins, they must be discarded only
points. Do not incinerate.
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Temperature (tc)
INDICATION LED STATUS (with the mains power supply connected)
CHARGE
Disconnected battery / not charging
Charged battery
Battery under charge
Indicator OFF
Page 2 from 3
contact the installer.
in battery recycling
LED CHARACTERISTICS
GRL-21
Cable connection between main pcb and led module
50 °C max.
Indicator ON
Indicator Blinking
Battery replacement.
It can be done only by a competent person and after the mains
interruption.
1. Follow the step 2 of the installation
procedure.
2. Disconnect the cables and remove the old
battery.
3. Connect the new battery with the same type
(step 3 of the installation procedure) and
place it in the position of the old one.
4. Follow the step 5 of the installation
procedure and power the device.
The
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
0: Non Maintained (*)
(*) Non Maintained operation: The luminaire lights its illumination
A:
Including test device
source, only in power supply's failure.
*90: 1.5 hour duration
Maintained operation: The luminaire lights its illumination source, when
180: 3 hours duration
it is powered by the mains power supply or not.
Olympia Electronics S.A.
2605163
20-25V
2.8W
POWER
No mains power supply
Normal operation mode
GRL-29
2002163
20-25V
5.5W
60 °C max.
923029009_09_012