 Overflow control
• Triggering condition
The float switch is turned on.
• Operation details
– The drain pump is turned on.
– When the operation mode is cooling or dry, operate the followings.
• The compressor is stopped.
• Then indoor fan control is turned off.
• Release condition
– The float switch is turned off.
• In the case that on the cooling or dry mode the thermostat is on, refer to
pressor in
• In other case, refer to
release.
– 3 minutes passed
• Operation after release
The compressor stopps permanently.
 The compressor is stopped by Anti-freezing control
• Triggering condition
During the compressor in operation, the compressor is stopped by Anti-freezing control.
• Operation details
The drain pump is kept on in 60 minutes after Anti-freezing control released.
• Release condition
60 minutes passed
• Operation after release
According to the settings, operate the followings.
a. Operation at
anti-freezing
b. Operation when
cooling mode is
stopped
Operation at
a. and b.
7-8. Drain pump control
operation" for the operation after release.
"When the compressor is not in
Anti-freezing start
Stopped
60
On
Off
3
7
On
Off
60
On
Off
operation" for the operation after
Release
freezing
3
47
3
2
3
- (04-30) -
"During the com-
3
117
117
3
(min)
7. Various control