Fujitsu AUXG36KRLB Service Manual page 12

Cassette type
Hide thumbs Also See for AUXG36KRLB:
Table of Contents

Advertisement

¢ Installation space requirement
H1
AUXG36-54KRLB
Be sure to make function setting with the remote controller according to the installed ceiling height.
Ceiling height
Standard
High ceiling
 Installation notices
• When installing the indoor unit, be careful about the maintenance space.
• To set "3-direction", Air outlet shutter plate (option) must be installed, and the "outlet-direction"
need to be switched to "3-way" by the remote controller.
• In 3-way outlet mode, changing of ceiling height setting by function setting 20 is prohibited. (Ceil-
ing height setting [function setting 20] is allowed to be changed only in 4-way outlet mode.)
• Use the Insulation kit for high humidity (option), when the condition under the roof is over 80% in
humidity and over 30°C in temperature. Otherwise, there is a risk of condensation on the ceiling.
2-1. Indoor unit
Strong and durable ceiling
3,000 or more
1,000 or more
Floor
Model name
H2: The maximum height from floor to ceiling
4 directions
1,800 to H2
Obstruction
Model name
AUXG36-54KRLB
3,200
4,200
100 or more
3 directions
Piping position
- (01-6) -
Unit: mm
1,500 or more
H1: Attic height
298 or more
2. Dimensions