Checklist for PZ-52SF-E ( Table 3-2 )
No.
Error
1 Nothing displays on the
LCD.
2 Continues to display
"HO" and does not start.
3 Cannot register the
Lossnay with PZ-
52SF-E or MELANS.
4 Starts or stops, or the
display changes, by itself.
5 Displays an error code
that is not in the checklist.
6 Cannot stop Lossnay
with the remote con-
troller. ("CENTRAL" is
displayed)
Note: PZ-60DR-E and PZ-52SF-E cannot be used in the same group.
Cause
Transmission cable is connected to the
wrong terminal block.
There is no power supply unit (for Lossnay
only systems).
The power supply unit is not turned on.
Transmission cable is not securely connected.
Wiring length of the transmission cable from the
power supply unit or the outdoor unit is longer than
specified (maximum extension 219 yd. (200 m)).
It is less than 10 minutes since the power
was supplied to the system.
Group setting (registration) has not been
performed.
The PZ-52SF-E address has not been regis-
tered in the group setting by MELANS.
Power supply to the Lossnay is not turned on.
Power that does not follow specifications is used.
Transmission cable is connected to the
wrong terminal of the Lossnay unit.
Lossnay address was changed.
Lossnay circuit board was replaced.
The length of the transmission cable wiring
is longer than specified (longer than maxi-
mum extension 219 yd. (200 m), longer than
547 yd. (500 m) between ends).
Power is not supplied to Lossnay.
Power that does not follow specifications is used.
Transmission cable to the Lossnay is not
connected.
Transmission cable is connected to the
wrong terminal of the Lossnay unit.
Lossnay address was changed.
The length of the transmission cable wiring
is longer than specified (longer than maxi-
mum extension 219 yd. (200 m), longer than
547 yd. (500 m) between ends).
The Lossnay unit is set for interlock opera-
tion with City Multi.
Liquid crystal display characters on the
remote controller are missing.
Operation of the remote controller has been
prohibited by MELANS.
"INTERLOCK MODE" is set to "oUT" (exter-
nal input given priority).
Remote/local switching (CN32) is set to
"Remote."
─ 51 ─
Action
Check the transmission cable
connection (TB5 A , B for M-NET
transmission cables).
Install the power supply unit.
Check the power to the power supply unit.
Check the transmission cable connection.
Check the length of the transmission
cable wiring. (See the technical manu-
al for details about the regulations.)
After supplying power to the system,
"HO" blinks for a maximum of about
10 minutes. (This is not an error.)
Perform the group setting (regis-
tration). If using MELANS, register
with the MELANS. If there is only
PZ-52SF-E, register with it.
Check the group setting with the
MELANS.
Check the power supply to Lossnay.
Check the power supply.
Check the transmission cable
connection (TB5
A
,
transmission cables).
Check the Lossnay address.
If the circuit board has been
replaced, perform the group set-
tings again.
Check the length of the transmis-
sion cable wiring. (See the tech-
nical manual for details about the
regulations.)
Check the power supply to Lossnay.
Check the power supply.
Check the transmission cable
connection.
Check the transmission cable
connection (TB5
,
A
transmission cables).
Check the Lossnay address.
Check the length of the transmis-
sion cable wiring. (See the tech-
nical manual for details about the
regulations.)
Cancel the interlock mode set-
ting.
Replace the remote controller.
Check the settings of the
MELANS.
Check the interlock mode setting.
(Refer to page 24)
Check the remote/local switching
(CN32). (Refer to page 27)
B
for M-NET
for M-NET
B