6 Ventilation mode change recommendation (RECOMMENDED, VENTILATION MODE) display
When PZ-60DR-E is used and the ventilation mode is set to Lossnay ventilation or bypass ventilation,
"RECOMMENDED" and "VENTILATION MODE" may be displayed alternately (for 10 minutes maximum).
This function informs the user of the suitable ventilation mode according to the automatic ventilation algo-
rithm. When a ventilation mode change recommendation has been displayed, more comfortable ventilation
can be provided by pressing the "Function selector" button of the remote controller and switching to another
ventilation mode.
( We r ecommend that "AUTO" be selected for the ventilation mode; however, there is no problem in leaving
the ventilation mode unchanged with "RECOMMENDED" "VENTILATION MODE" displayed.)
( 5 ) Interlocking with external devices
1 Input signal
The system will interlock with the following input signals from external devices and start/stop.
systems having multiple Lossnay units, input the signal to the "Main" Lossnay.
Multiple units
Type
Level signal
Charged 12 V DC/24 V DC
Operation signal: 12 V DC/24 V DC
Stop signal
Uncharged a-contact
( Current drawn: 10 mA or greater )
Operation signal: Close
Stop signal
Pulse signal
Charged
Uncharged a-contact
Start/stop is inverted with each
pulse
Systems
• Connect the signal cable of Mr. Slim to Lossnay, and per-
interlocked
form the Lossnay interlock settings from the A-control remote
with Mr.
controller or the K-control remote controller.
Slim
• The system is started/stopped by interlocking with Start/
Stop of the A-control remote controller or K-control remote
controller.
• The system is started/stopped by interlocking with the venti-
lation setting of the A-control remote controller.
• The Mr. Slim operation mode, target temperature, and other
internal information can also be brought in.
Systems
• City Multi indoor units and Lossnay are connected by
interlocked
M-NET, and the Lossnay interlock setting is performed by the
with
remote controller or system controller.
Mitsubishi
• The system is started/stopped by interlocking with Start/
City Multi
Stop of the MA remote controller or ME remote controller and
indoor units
the ventilation setting.
• The City Multi indoor unit operation mode, target tempera-
ture, and other internal information can also be brought in.
Signal, and operation
: 0 V
: Open
12 V DC/24 V DC
Pulse width 200 ms or greater
─ 23 ─
Setting Method
PZ-60DR-E
PZ-60DR-E Not Used
( Remote controller
( Function selec-
function selection )
tion switch )
Pulse input setting
SW2-2: OFF
"oFF"
Pulse input setting
SW2-2: ON
"on"
PZ-60DR-E
SW2-2: OFF
( Lossnay remote
controller ) can-
not be used.
Pulse input setting
SW2-2: OFF
"oFF"