( 3 ) Troubleshooting 3: The remote controller operation is disabled or irregular.
Checklist for PZ-60DR-E or PZ-41SLB-E ( Table 3-1 )
No.
Error
1 Nothing displays on the
LCD.
2 Starts or stops, or the
display changes, by
itself.
3 Displays an error code
that is not in the check
list.
4 Cannot stop the
Lossnay with the remote
controller. ("CENTRAL"
is displayed)
5 Cannot stop the Lossnay
with PZ-60DR-E. ("24HR
VENTILATION" is displayed).
6 Cannot switch fan speed
with the remote control-
ler.
Cause
Transmission cable is connected to the
wrong terminal block.
No Lossnay unit is set to "Main".
Power is not supplied to Lossnay.
Power that does not follow specifications is used.
Transmission cable is not securely connected.
The length of the transmission cable wiring is long-
er than specified (longer than 547 yd. (500 m)).
Multiple transmission cables are wired with
multi core cables.
Transmission cable and power supply cable
are too close.
Liquid crystal display characters on the
remote controller are missing.
Poor return action of the remote controller buttons.
Operation of the remote controller has been
prohibited by MELANS.
"INTERLOCK MODE" is set to "oUT" (exter-
nal input given priority).
Remote/local switching (CN32) is set to
"Remote."
24-hour ventilation is set to " on" with the
PZ-60DR-E function selection.
High/Low/Extra Low fan speed switching
external input (CN16) is ON.
When PZ-60DR-E is used, "POWER VENT
START" is set to " on" with the function se-
lection of the remote controller.
When PZ-60DR-E is not used, the function
selection switch for "Power supply/exhaust
when operation starts" (SW2-3) on the
Lossnay circuit board is set to ON.
When PZ-60DR-E is used, the supply fan
speed setting and the exhaust fan speed
setting are set to "L" with the function selec-
tion of the remote controller.
When PZ-60DR-E is not used, the function selec-
tion switches for "Supply fan fixed at Low speed",
and "Exhaust fan fixed at Low speed" (SW2-4,
SW2-5) on the Lossnay circuit board are set to ON.
In a mixture of the LGH-F300 to F600 types
and the LGH-F1200 type, the LGH-F1200
type is set to "Main" . (Extra Low fan speed
operation is not available.)
─ 49 ─
Action
Check the transmission cable con-
nection. (TM4 1, 2 for the transmis-
sion cable from the remote controller)
Turn off the main power supply and
set the Main/Sub selection switch
(SW1) (first unit to "Main", and sec-
ond and following units to "Sub").
Check the power supply to Lossnay.
Check the power supply.
Check the transmission cable connection.
Check the length of the transmis-
sion cable wiring.
Use suitable cables to wire the
transmission cables so that they
are separated from one another.
Wire the transmission cable at
least 2 in. (5 cm) away from the
power supply cable.
Replace the remote controller.
Replace the remote controller.
Check the setting of the
MELANS.
Check the interlock mode setting.
(Refer to page 24)
Check the remote/local switching
(CN32). (Refer to page 27)
Check the 24-hour ventilation
setting with the PZ-60DR-E func-
tion selection. (Refer to page 32)
Check the High/Low/Extra Low
fan speed switching input (CN16).
(Refer to page 25 and 26)
Check the setting of " power
supply/exhaust when operation
starts" with the PZ-60DR-E func-
tion selection. (Refer to page 33)
Check the function selection
switch (SW2-3). (Refer to page
30)
Check the supply fan speed set-
ting and the exhaust fan speed
setting with the PZ-60DR-E func-
tion selection. (Refer to page 33)
Check the function selection
switches (SW2-4, SW2-5). (Refer
to page 30)
Set the LGH-F300 to F600 types
to "Main" and the LGH-F1200
type to "Sub" . (Refer to page 31)