[1] For operating on High ( Extra High ) fan speed via external input
Usually, ventilation is performed at Low/Extra Low fan speed, and there is automatic switching to High
( Extra High ) fan speed when dirty indoor air is detected by a CO
Insert the remote display adaptor ( PAC-SA88HA-E ) into the connector ( CN16 ) on the Lossnay circuit
board, and input the signal ( uncharged a-contact ) from the CO
When the contacts in the diagram below are ON ( closed ) , the system will switch to High ( Extra High ) fan
speed regardless of the fan speed settings on the remote controller or the system controller.
CO
sensor, etc.
2
(At the time of CO
2
Contact rating: 15 V DC, 0.1 A or greater
Minimum applicable load: 1 mA or less
[2] For operating on Low fan speed via external input
Usually, ventilation is performed at High ( Extra High ) fan speed, and there is automatic switching to Low
fan speed when an absence of dirty indoor air is detected by a CO
Insert the remote display adaptor ( PAC-SA88HA-E ) into the connector ( CN16 ) on the Lossnay circuit
board, and input the signal ( uncharged a-contact ) from the CO
When the contacts in the diagram below are ON ( closed ) , the system will switch to Low fan speed
regardless of the fan speed settings on the remote controller or the system controller.
CO
sensor, etc.
2
(At the time of CO
decrease: Close)
2
Contact rating: 15 V DC, 0.1 A or greater
Minimum applicable load: 1 mA or less
Wiring length within 32.8 in. (10 m)
[3] For operating on Extra Low fan speed via external input ( The LGH-F1200 type cannot be used )
Usually, ventilation is performed at High ( Extra High ) /Low fan speed, and there is automatic switching to
Extra Low fan speed when an absence of dirty indoor air is detected by a CO
Insert the remote display adaptor ( PAC-SA88HA-E ) into the connector ( CN16 ) on the Lossnay circuit
board, and input the signal ( uncharged a-contact ) from the CO
When the contacts in the diagram below are ON ( closed ) , the system will switch to Extra Low fan speed
regardless of the fan speed settings on the remote controller or the system controller.
CO
sensor, etc.
2
(At the time of CO
decrease: Close)
2
Contact rating: 15 V DC, 0.1 A or greater
Minimum applicable load: 1 mA or less
Wiring length within 32.8 in. (10 m)
increase: Close)
Insulation
processing
Wiring length within 32.8 in. (10 m)
Insulation
processing
Insulation
processing
sensor, etc.
2
sensor to the brown and red lines.
2
Remote display adaptor
(Sold separately)
PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
sensor to the brown and orange lines.
2
Remote display adaptor
(Sold separately)
PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
sensor to the brown and yellow lines.
2
Remote display adaptor
(Sold separately)
PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4
Green 5
─ 26 ─
Lossnay circuit board
CN16
Fan speed/ventilation
mode switching
sensor, etc.
2
Lossnay circuit board
CN16
Fan speed /ventilation
mode switching
sensor, etc.
2
Lossnay circuit board
CN16
Fan speed/ventilation
mode switching