( 6 ) External input/output terminals on the Lossnay circuit board
Located on the Lossnay circuit board are terminals for the external output of the Lossnay operating condition,
and input terminals for external switching of the Lossnay fan speed and ventilation mode.
1 Output terminals
The function and contact rating of each output terminal are described below.
"Operation monitor" and "Bypass operation monitor" are in common with "Operation monitor with delay
function 1" and "Operation monitor with delay function 2", respectively.
( Switch with the DIP switch on the Lossnay circuit board. Refer to page 30 and 31. )
Output
Turned ON ( closed ) at time
Malfunction moni-
tor
of Lossnay malfunction.
Turned ON ( closed ) at time
Operation monitor
*3
of Lossnay operation.
This can also be turned ON
( closed ) at time of air sup-
ply fan operation.
Turned ON ( closed ) 10 sec-
Operation monitor
with delay function
onds after start of air supply
1
fan.
Turned ON ( closed ) at time
Bypass operation
monitor
of bypass ventilation.
Operation
Turned ON (closed) 10 sec-
monitor with delay
onds after start of air supply
function 2
fan when outdoor air temper-
ature is 23°F (-5°C) or lower.
Turned OFF (open) when
outdoor air temperature is
59°F (15°C) or higher.
*1 Terminal 7 of TM3 is a common terminal with bypass operation monitor/operation monitor with delay func-
tion 2 output 7.
*2 Terminal 7 of TM3 is a common terminal with malfunction monitor output 7.
*3 The operation monitor can also be used as an air supply fan operation monitor with the setting described
below.
< When using PZ-60DR-E >
< When not using PZ-60DR-E >
Input terminals
2
a. High/Low/Extra Low fan speed switching input
This is used for external switching of the fan speed by means of a commercially available CO
During the input of High ( Extra High ) /Low/Extra Low fan speed selection, PZ-60DR-E displays
Operation
"Automatic Fan Speed" indicator. The set fan speed cannot be changed while "Automatic Fan
Speed" is displayed due to operation restrictions. Other remote controllers and system control-
lers can change the fan speed display; however, the fan will remain fixed at the input fan speed
selection of High ( Extra High ) /Low/Extra Low.
When PZ-60DR-E is used in a system of multiple Lossnay units, input of High ( Extra High ) /Low/
Multiple
Extra Low fan speed into the "Main" Lossnay will permit the switching of the fan speed of all
units
Lossnay units within the same group. When PZ-60DR-E is not used, input High/Low/Extra Low
fan speed into each Lossnay unit. In this case, the setting is applied only to the Lossnay units
that have received the High/Low/Extra Low input.
• A remote display adaptor ( PAC-SA88HA-E ) , which is sold separately, is required for the connections.
• The input of the Extra Low fan speed is not available for the LGH-F1200 type.
Output
Function
Terminal
TM3 7, 8
*1
TM4 9, 0 Uncharged
TM3 6, 7
*2
Set "2" for operation monitor output of function selection.
Set the operation monitor output switch on the Lossnay circuit board
( SW5-2 ) to ON. ( This function cannot be used when operation monitor
with delay function 1 has been set. )
─ 25 ─
Signal
Form
Maximum
Uncharged
230 V AC, 1 A
a-contact
24 V DC, 1 A
230 V AC, 2 A
a-contact
24 V DC, 2 A
Uncharged
230 V AC, 1 A
a-contact
24 V DC, 1 A
Contact Rating
Minimum
208 V AC, 100 mA
5 V DC, 100 mA
208 V AC, 100 mA
5 V DC, 100 mA
208 V AC, 100 mA
5 V DC, 100 mA
sensor, etc.
2