Drain pipe and Drain Hose Installation
Drainpipe Connection
1. The drain pipe should be installed within 100mm from the flexible hose, lift up from 100mm to 550mm and lift
down 20mm or more.
2. Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1~1.5m.
3. Install the air vent in the horizontal drainpipe to prevent water flow back to the indoor unit.
• You may not need to install it if there were proper slope in the horizontal drainpipe.
NOTE
4. The flexible hose should not be installed upward position, it may cause water flow back to the indoor unit.
5. Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.
Flexible hose Installation
Be horizontal
Indoor
Unit
• Install horizontally
Indoor
Unit
• Max. allowable bending angle
20
DVM S NASA_Global 4-WC_사우디향_IM_EN_04191A.indd 20
Air vent
300mm or less
Flexible hose
100~550mm
or less
Horizontal drainpipe more
Flexible hose
Max. 30˚
1~1.5m
Hanger
than 1/100 slope
Ceiling
Indoor
Unit
• Max. allowable axis gap
Insulation
Connect to
indoor unit
Insulation
Flexible hose
(Apply adhesive
on the outside)
• Handle with using adhesive not to block the inside
of flexible hose
Max. 20mm
Connect to PVC
drain pipe
PVC drain pipe
(Apply adhesive
on the inside)
2013-11-05 오전 11:30:25