Correcting Communication Failures; Iec Communication Problems - Siemens NK8237 MP4.81-02 Installation, Configuration And Commissioning

For sinteso and cerberus pro fire detection systems
Table of Contents

Advertisement

Maintenance and diagnostics
9

Correcting communication failures

11.3
11.3.1
76
Building Technologies
CPS Fire Safety
Configuring logging function on the fly
Note: The reset of the unit results in restoring the original logging configuration
saved in Composer.
Correcting communication failures

IEC communication problems

Communication faults on the IEC may depend on different causes. The problem
can occur in the NK8237 unit or in the connections.
Check the NK8237
Check power, vital function, and diagnostic state of the corresponding LED located
on the front panel.
Note: If you need to modify the IP address because of a network change, you
might want to reset the device back to factory configuration by setting DIP-switch
1 or 2 to ON (see Internal DIP switches [➙ 17]) and then connect using the known
address to change the IP address.
Check the network connections (IEC TCP/IP)
LAN
Diagnostic information about the LAN state can be obtained from different
layers:
Link state LED of Repeater or Ethernet adapters gives you information about
the physical connection and the speed of the Ethernet link.
1) Select Start > Programs > Accessories > Command Prompt.
2) Choose from the following commands:
A6V10854379_a_en
25.01.2019