Siemens NK8237 MP4.81-02 Installation, Configuration And Commissioning page 50

For sinteso and cerberus pro fire detection systems
Table of Contents

Advertisement

Configuration
7
Configuring the Fire network
50
Building Technologies
CPS Fire Safety
Example of FS20 Station BACnet settings
Setting the FC20xx/FC72x Ack/Reset mode
Acknowledgement and reset commands can only be set as general actions in the
IEC Gateway. This means that the commands apply to all the pending events of
the affected control unit.
1. Select the FC20xx/FC72x Node tab.
2. Make sure to select the General Acknowledgement and General Reset options
(default setting).
Note: The parameter settings for the Single Event Acknowledgement and Single
Event Reset are not supported by NK8237 and must not be used.
A6V10854379_a_en
25.01.2019