Appendix I. Model Number Nomenclature − Horizontal - Bryant 580J D17 Service And Maintenance Instructions

Gas heat packaged rooftop nominal 15 to 27.5 tons with puron r-410a refreigerant
Table of Contents

Advertisement

APPENDIX I. MODEL NUMBER NOMENCLATURE − HORIZONTAL
Position:
1
Example:
5
Unit Type
580 - Gas Heat RTU
Model
J - Puron
®
(R-410A) Refrigerant
Voltage
E = 460-3-60
P = 208/230-3-60
T = 575-3-60
Cooling Tons
18 - 15 tons
21 - 17.5 tons
25 - 20 tons
29 - 25 tons
Refrig. System/Gas Heat Options
D = Two stage compressor model
F = Two stage compressor model and Stainless Steel
gas heat exchanger
K = Two stage cooling with Aluminum gas heat exchanger
and Perfect Humidity™
M = Two stage cooling with Stainless Steel gas heat
exchanger and Perfect Humidity™
Heat Level Input
220 = 220,000
310 = 310,000
400 = 400,000
Coil Options (RTPF) (Outdoor - Indoor - Hail Guard)
A = Al/Cu - Al/Cu
B = Precoat Al/Cu - Al/Cu
C = E-coat Al/Cu - Al/Cu
D = E-coat Al/Cu - E-coat Al/Cu
E = Cu/Cu - Al/Cu
F = Cu/Cu - Cu/Cu
M = Al/Cu -Al/Cu — Louvered Hail Guard
N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard
P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard
Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard
R = Cu/Cu - Al/Cu — Louvered Hail Guard
S = Cu/Cu - Cu/Cu — Louvered Hail Guard
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17
8
0
J
E
1
8
D
3
1
0
A
5
A
0
A
A
Packaging & 2-Speed Indoor Fan Motor
A = Standard Packaging, electro mechanical
C = Standard Packaging, electro mechanical
D = Standard Packaging & 2-speed indoor
Factory Installed Options
0A = None
NOTE: See the 580J Horizontal Models
Outdoor Air Options
A = None
B = Temperature Economizer, Barometric Relief,
Standard Leak (W7212 or W7220)
E = Temperature Economizer, Barometric Relief,
Standard Leak w/CO
H = Enthalpy Economizer, Barometric Relief,
Standard Leak (W7212 or W7220)
L = Enthalpy Economizer, Barometric Relief,
Standard Leak w/CO
P = Manual Outdoor Air Damper
Q = Motorized 2 Position Damper
U = Temperature Economizer, Barometric Relief,
Ultra Low Leak (W7220)
V = Temperature Economizer, Centrifugal Power Exhaust,
Ultra Low Leak (W7220)
W = Enthalpy Economizer, Barometric Relief, Ultra Low Leak
(7220)
Indoor Fan Options
5 = Standard Static/HorizontalSupply, Return Air Flow
(except on size 29)
6 = Medium Static/Horizontal Supply, Return Air Flow
7 = High Static/Horizontal Supply, Return Air Flow
F = Medium Static High Efficiency Motor/Horizontal Supply,
Return Air Flow (Standard on 29 size models)
G = High Static High Efficiency Motor/Horizontal Supply,
Return Air Flow
62
controls that require W7212 EconoMi$er IV
controls that require W7220 EconoMi$er X
fan motor (Standard on 29 size models)
15 to 25 ton Price Pages for a
complete list of factory installed options.
(W7212 or W7220)
2
(W7212 or W7220)
2
C13804C