User Guide | Intelligent Purging System (IPS 8) Ammonia
Register Parameter Name
UNIT CONFIG >
VALVE SETTINGS
3022
Max_PP
UNIT CONFIG >
LIMITS SETTINGS
3034
Setpoint
3035
Tsh
STATUS VAR > MCX
DESIGN HOTSPOTS
1859
Reset Alarms
8101
SystemOnOff
8102
ValveStatus
8103
CompressorStatus
8104
ALARActive
8105
PressTotemp
8106
ValveCount
8108
ComprTime
8110
COmprStartAfter
Advanced Setting -
9901
ResetMem
8112
ValveHour
8114
StatusKL
8115
WaringCompr
8116
ValveSetpoint
8117
ValveClose
8119
Event1
8121
Event2
© Danfoss | DCS (ms) | 2021.04
User
Description
Level
Used amount of purge
points - part of initial
2
setup
Pressure threshhold
2
for compressor
Setpoint for superheat
2
Reset alarm
0
Feedback from the
0
main switch
Feedback from the
purge valve - open/
0
closed
Feedback from the
0
compressor - on/off
Any alarm active
0
indicator
Suction temperature
(calculated from
0
pressure on suction)
The amount of purge
0
valve activations
Remaining time for
compressor pull-down
0
for the actual purge
pointr cycle
The delay between
0
the purging cycles
Recommend default
setting only - All
logged values are
0
reset
0: NO
1: YES
The amount of hours
that the main purge
0
-214748364,8 214748364,7
valve has been active
Status of KL01 relay
(compressor and
0
crankcase heater)
Indicates problem
with compressor
0
status
Temperature
threshhold for the
0
opening of the main
purge valve
Temperature
threshhold for the
0
closing of the main
purge valve
Purge cycle event -
counts the minutes
that the purge valve
0
has been open on a
finished cycle
Purge cycle event -
counts the accumative
minutes that the
0
purge valve has been
open on a finished
cycle
Default
Min Value
Max Value
Value
0
8
8
0,0
12,0
6.5
5,0
40,0
15
0
2
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-32768
32767
0
-327,7
327,7
0
-2147483648
2147483647
0
-2147483648
2147483647
0
-2147483648
2147483647
0
0
1
0
0
-32768
32767
0
-32768
32767
0
-2147483648
2147483647
0
-2147483648
2147483647
0
-3276,8
3276,7
0
-3276,8
3276,7
0
Modbus
Unit/
Read/
Modbus
Function
Type
Write
Data Type
Code
N/A
RW
3/6
Short
bar
R/W
3/6
Short
°C
R/W
3/6
Short
N/A
R/W
3/6
Short
Read
Enum 1
3
Short
only
Read
Enum 1
3
Short
only
Enum 1
R/W
3/6
Short
Read
Enum 2
3
Short
only
Read
°C
3
Short
only
Read
N/A
3
Long
only
Read
Minutes
3
Long
only
Read
Minutes
3
Long
only
Enum 2
R/W
3/6
Short
Read
Hours
3
Long
only
Read
Enum 2
3
Short
only
Read
Enum 2
3
Short
only
Read
°C
3
Short
only
Read
°C
3
Long
only
Read
Minutes
3
Long
only
Read
Minutes
3
Long
only
BC344024774466en-000401 | 21
Persistent
Yes/No
Yes
Yes
Yes
Yes
No
No
Yes
No
No
No
No
No
Yes
No
No
No
No
No
No
No