Configuring The Equipment Settings - Reversing Valve - Verdant VX-TW Network Installation

Hide thumbs Also See for VX-TW:
Table of Contents

Advertisement

configuring thermostats
11.

Configuring the Equipment Settings - Reversing Valve

Use the "Up" and "Down" buttons to change the reversing Valve
setting by changing the third digit;
0
energizes the PtAc Ob valve to cOOL;
1 *
energizes the PtAc Ob valve to HeAt;
refer to the PtAc unit documentation to determine the correct Ob
VALVe setting.
If incorrect Ob VALVe Setting is selected, the PtAc unit will turn on
the heating when air conditioning is requested and turn on the air
conditioning when heating is requested;
Press the "Fan" button to advance to the next setting;
Press the "F/c" button to advance to the next menu;
Verdant VX-tW Network Installation
REVERSING VALVE