CONTENTS A5VR CAREFREE SERIES A5VR030DRM•A5VR035DRM• A5VR040DRM•A5VR050DRM• A5VR060DRM•A5VR065DRM• A5VR070DRM•A5VR080DRM NOMENCLATURE 1.1 OUTDOOR 1.2 INDOOR APPLICATION INFORMATION 2.1 REFRIGERANT CIRCUIT DIAGRAM 2.2 INSTALLATION GUIDELINE ENGINEERING & PHYSICAL DATA PERFORMANCE CURVE 4.1 CAPACITY DROP DIAGRAM OUTLINE & DIMENSION WIRING DIAGRAM SERVICE & MAINTENANCE TROUBLESHOOTING * All specifications stated in this technical manual are for Cooling Only unit.
Page 3
NOMENCLATURE A5VR Carefree series units are most suitable for commercial building, office room, hotel, which includes the outdoor units and multi-indoor units. The advantage of this product range is unique outdoor units with inverter compressor. To meet different requirements, there are many indoor units to be chosen: ceiling concealed, ceiling cassette, wall mounted, ducted blower and ceiling mounted;...
Page 4
Ceiling Cassette Indoor Units: A5VCK-V Series Product Range: A5VCK028V, A5VCK032V, A5VCK036V, A5VCK040V, A5VCK045V, A5VCK050V, A5VCK056V, A5VCK063V, A5VCK071V, A5VCK080V, A5VCK090V, A5VCK100V, A5VCK112V, A5VCK125V, A5VCK140V Feature: 4 ways air supply evenly, streamlined design, in-build high efficiency filter; Nomenclature A 5 V CK 028 V - 07 A IA E Applied region (Omitted: China, D:Hong Kong, E:Other region) Description of the unit Power supply features A:220V~/50Hz...
Page 5
Ducted Blower Indoors Units: A5VDB-V Series Product Range: A5VDB125V, A5VDB140V, A5VDB224V Feature: Installed above ceiling with air supply duct working, meet the requirement for long distance air supply; Nomenclature A 5 V DB 125 V - A IA E Applied region (Omitted: China, D:Hong Kong, E:Other region) Description of the unit Power supply features A:220V~/50Hz Series V: V series...
2.2 Installation Guideline (Outdoor Clearance) Space for installation of outdoor units Single outdoor unit can be installed in one place, and multiple outdoor units can be installed together in one larger place. Please reserve the minimum installation space, the units may not operate properly if the space is smaller than required.
Page 8
Figure 4 Figure 5 Figure 6 2.2.2 Obstacle exists at the air exhaust side No obstacle exists at upper side a. Single unit installation (see Figure 7) b. Group units installation (more than two units) (see Figure 8) • Obstacle exists at upper side a.
Page 9
b. Group units installation (more than two units)(see Figure 10) Figure 10 2.2.3 Obstacles exist at the air exhaust and intake side Model 1: The height of obstacle at intake side is absolute ,when the obstacle at exhaust side is higher than units.
Page 10
• Obstacles exist at upper side a. Single unit installation (see Figure 13) The relation of H, A, L is as follows: 0 < L ≤ 1/2H L ≤ H 1/2H < L ≤ H 1000 H < L The setting of foundation is L ≤ H Seal the bottom of foundation to prevent the exhausted air from crossing the unit.
Page 11
Model 2: The height of obstacle at intake side is absolute ,when the obstacle at exhaust side is lower than units. • No obstacle exists at upper side a. Single unit installation (see Figure 15) L ≤ H b. Group units installation (more than two units)(see Figure 16) The relation of H, A, L is as follows: 0 <...
Page 12
Seal the bottom of foundation to prevent the exhausted air from crossing the unit. b. Group units installation (more than two units)(see Figure 18) The relation of H, A, L is as follows: 0 < L ≤ 1/2H L ≤ H 1/2H <...
Page 13
Figure 19 Figure 20 2.2.5 Multi-lined group installation (In the roof, etc.) • Multi-lined single installation (see Figure 21) • Multi-lined group installation (more than two units a group)(see Figure 22) The relation of H, A, L is as follows: 0 <...
Page 15
Ceiling Cassette Indoor Units A5VCK A5VCK A5VCK A5VCK A5VCK A5VCK A5VCK A5VCK A5VCK Model 028V 032V 036V 040V 045V 050V 056V 063V 071V Power Supply 220V ~ /50Hz Normal Intersection Surface(mm Cable Electrical heater Quantities A5VCK A5VCK A5VCK A5VCK A5VCK A5VCK Model 080V...
Page 16
Ducted Blower Indoor Units Model A5VDB125V A5VDB140V A5VDB224V Power Supply 220V ~ /50Hz 380V/3N~/50Hz Intersection Normal Surface(mm Cable Quantities Note: • The lead-in position of power cable must be provided a short circuit device with a sufficient capacity. This device has a contact separation of 3 mm at least. •...
Page 17
2.2 Installation Guideline (Refrigerant Piping) Refrigerant piping length limitations Bifurcation/Refnet Height difference between Height difference between the indoor units indoor units and outdoor units Pipe Parts A5VR030DRM ≤80m L1+L2+... Total length Actual length +Li+a+b+…+i A5VR040 ~ A5VR080DRM ≤120m A5VR030DRM ≤50m Actual length Pipe A5VR040 ~ A5VR080DRM...
Page 18
Equivalent length refers to the elbow and other parts of the tube with consideration to the pressure lost after the conversion length. The formula is as follows: Equivalent length = actual length of pipe + number of elbows x Equivalent length of various elbows The length of each branch is 0.5m, with the equivalent length of the elbow as follows: Equivalent length Equivalent length...
OUTLINE & DIMENSION A5VR030/035DRM Unit:mm Model A5VR030/035DRM 4-R7.5 A5VR040/050/060/065/070/080DRM Unit:mm Model A5VR040/050/060DRM 1196 1222 4-R7.5 A5VR065/070/080DRM 1328 1354 4-R7.5 Unit:mm...
Page 29
A5VCK028/036/045/056/071/080/090/100/112/125/140V Unit:mm Model A5VCK028/036/045/056/071V A5VCK080/090/100/112/125/140V A5VCC022/025/028/032/036/040/045/050/056/063/071V (Ultra Thin) Unit:mm Model Fan Amount A5VCC022V A5VCC025/028/032/036V 763.5 A5VCC040/045/050/056V A5VCC063/071V 963.5 1100 1162 1140 Note: return air inlet size is Inner-space size. Back air return plenum: Air Inlet Air Outet...
Page 30
Bottom air return plenum: Air Outet Air Inlet A5VCC080/090/100/112/125/140/160V (Standard Type) Unit:mm Model Amount A5VCC080V 1314 1005 A5VCC090/100 1300 1331 1664 1355 1314 /112/125V A5VCC140/160V 1560 1591 1924 1615 1574 Air Outet Air Inlet...
Page 31
Bottom air return plenum: Air Outet Air Inlet Free-stream air return plenum:...
Page 32
A5VDB125/140V Unit:mm Model Fan Amount A5VDB125V 1004 1044 1078 1227 A5VDB140V 1150 1204 1244 1278 1427 6-12x20 A5VDB224V Unit:mm Model Fan Amount A5VDB224V 1681 1399 1760...
SERVICE & MAINTENANCE Warning Before maintenance service, please shut off the power supply and stop indoor and outdoor units Indoor Unit Maintenance Times/month Part Maintenance Checking step (Recommend) 1. Open the grille 2. Take out the air filter 3. Use brush to clean the air filter with below 40°C water Air filter 4.
Page 40
Status Display Of Digital Tubes Four 8-section 4-bit digital tubes (red) are configured for the outdoor unit. In the normal running status, the digital tube displays the current running mode or status. Once any fault occurs, the fault code is displayed first.
Page 41
dEb: button debugging parameter menu. SPEC: special button function menu. NOAE: night noises reduction function. FAC: Restore factory settings. BAUD:Set communication speed of units and PC. PreH: The compressor pre-heating status. CFEE: Set the function of household billing. IGNO: Leave alone the very unavailable unit. FSPD: Choose proper fan gear table (15/30).
TROUBLESHOOTING If the following unit malfunction occurred, please follow the below simple checking step to fix : Symptom Analyses Solution Indoor temperature is higher (heating) or lower (cooling) than Compressor stop Re – set up the temperature setting temperature and fan work normally When heating and defrost mode, indoor unit is just running Wait for 10minutes...
Page 43
Displayed Fault of Lamp Panel Fault Fault Description Code HEAT DRY/TIMER SLEEP/FAN Fault codes of the indoor unit part: Coil inlet sensor malfunction Blinking Coil middle sensor malfunction Blinking Coil outlet sensor malfunction Blinking Air return/room sensor malfunction Blinking Condensate pump (water level switch) malfunction Blinking Blinking EEPROM storage malfunction of indoor unit...
Page 44
DSP and communication board communication malfunction Blinking Outdoor unit and drive board communication malfunction Blinking Compressor over-current alarm Compressor weak magnetic protection alarm Blinking Radiator overheating alarm AC input over-current alarm EEPROM of drive board malfunction alarm Blinking Compressor1 over-current alarm Blinking Compressor2 over-current alarm Blinking...
Page 45
Compressor2 discharge temperature exceeds allowed range Blinking Blinking Compressor1 current sensor malfunction Blinking Blinking Compressor2 current sensor malfunction Blinking Blinking Fire Alarm Blinking Blinking Stop malfunction due to ultra-low superheat degree of air exhaust Blinking Blinking Temperature sensor malfunction of main subcool outlet (TH10) Blinking Suction temperature sensor fault(TH12) Blinking...
Page 46
FAN1: Fatal malfunction Blinking Blinking Blinking Outdoor unit and drive board of fan1 communication malfunction Blinking Blinking Blinking FAN2: over-current Blinking Blinking Blinking FAN2:IPM malfunction Blinking Blinking Blinking FAN2: Drive stall Blinking Blinking Blinking FAN2: Lack phase Blinking Blinking Blinking FAN2: Speed loss Blinking Blinking...
Page 47
Displayed normal operating status of the lamp panel: Silk-screen Mode Cool Heat Timing Sleep A5VWM Green Yellow Silk-screen Cool Dry/Timing Heat Mode Cool Timing Sleep Heat A5VCC A5VDB Green Silk-screen Mode Cool Heat Timing Sleep A5VCK Green Yellow Silk-screen Mode Cool Timing Sleep...
Page 48
ACSON MALAYSIA SALES & SERVICE SDN.BHD. (129688-D) DAIKIN a member of group Lot 4, Lorong 19/1A, Seksyen 19, 46300 Petaling Jaya, Authorized Dealer : Selangor Darul Ehsan, MALAYSIA. Tel : +603 7964 8200 Sales Fax : +603 7956 9909 Sernice Fax : +603 7956 9907 Acson Careline : 1300 22 3344 Penang : +604-5377 176 Pahang : +609 5178 696...