Inverter single split type outdoor air conditioner (70 pages)
Summary of Contents for Acson international A5WCP0060A-FP
Page 1
WATER COOLED SELF-CONTAINED AIR-CONDITIONER INSTALLATION, OPERATION, MAINTENANCE IOM NO: O-WCP15-SEP21-2 Scan QR code to download the latest version of IOM...
Page 2
IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. During installation, operation maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death.
1.0 INTRODUCTION This manual applies to Water Cooled Self Contained Units, Models A5WCP0060 to A5WCP0940. This manual provides specific instructions for installation, owner maintenances, and troubleshooting. Due to continuous product improvement and enhancements, the information provided is subject to change without notice.
2.0 INSTALLATION The unit is designed for indoor installation only. Installation of this unit must conform to local building codes and/or regulation. The unit shall be operated according the limit specified in Table 1. Table 1: Unit Operating Limit MAXIMUM WORKING SAFETY PRESSURE CONDENSER TEST PRESSURE (UNIT)
Unit weights are listed in Table 3. Refer to unit shipping weight for crane selection for rigging. Failure to fulfill the requirement might lead to hazardous. Table 3: Unit Weight MODEL SHIPPING OPERATING WEIGHT, KG WEIGHT, KG A5WCP0060A-FP A5WCP0090A-FP A5WCP0140A-FP A5WCP0180A-FP A5WCP0060A-FS A5WCP0090A-FS A5WCP0140A-FS A5WCP0180A-FS A5WCP0240A-FS...
The following guidelines should be used to select a suitable location for the unit lifting: 1. Determine the approximate center of gravity for lifting safety before lifting the unit. 2. Always test-lift the unit to determine the exact unit balance and stability before hoisting it to the installation location.
Page 11
Table 5: Performance Table ON COIL WATER OUTLET TEMPERATURE ( SOUND Wet Bulb Rated at ESP Bulb 250Pa Model Total Sensible Total Total Sensible Total Total Sensible Total SPLw Cooling Capacity Power Cooling Capacity Power Cooling Capacity Power dB(A) dB(A) Capacity (MBH) Input...
Page 12
Table 5: … Continue ON COIL WATER OUTLET TEMPERATURE ( SOUND Wet Bulb Rated at ESP Bulb 250Pa Model Total Sensible Total Total Sensible Total Total Sensible Total SPLw Cooling Capacity Power Cooling Capacity Power Cooling Capacity Power dB(A) dB(A) Capacity (MBH) Input...
5.2 DUCTING Supply Air For connection of supply ductwork directly to the unit, a duct collar must be mounted at the unit outlet. When connecting ductwork to the unit, a canvas type connecting collar is recommended. If a field fabricated plenum is used, canvas type connectors are recommended at the duct connection to the plenum. Units are also available with a factory provided discharge plenum.
Condenser Water Piping All internal condenser water piping is completed factory assembled. Field piping should be connected to the pipes that are stubbed out at the panels. Supply water must be connected to the factory piping as indicated by the markings on the unit. Condensate Drain Connections The condensate drain connection is located on the drain pan that forms the partition between the coil and condensing section.
5.5 SUPPLY AIR BLOWER ADJUSTMENT The RPM of the supply air blower will depend on the required CFM, the unit accessories and the static resistances of both the supply and the return air duct systems. With this information, the RPM for the supply air blower can be determined from fan performance curves.
6.0 ELECTRICAL CONNECTION Before performing any service/maintenance work on the unit, ensure that the power supply is switched off. Failure to do so may result in serious injury or death. Install electrical wiring in accordance with the National Electric Code and / or local regulations. A fused disconnect switch must be used in a separate circuit from the main power panel.
7.0 COMMISIONING PRE-STARTUP REQUIREMENTS 1. Inspect the unit for shipping or installation damage. 2. Verify the unit is completely and properly installed with ductwork connected. Verify that all construction debris is removed and filters are clean. 3. With all electrical disconnects open, check all electrical connections to be sure they are tight. 4.
Page 52
INITIAL START-UP After all the other preceding checks have been completed and the operator has familiarized himself with the sequence of operation for the unit and all options provided, the unit can be put in operation. Proceed as follows: 1. Energize cooling tower water pump and tower fans. Set the water flow rate according to the design value. 2.
8.0 MAINTENANCE A planned program of regularly scheduled maintenance will return dividends by averting possible costly and unexpected periods of down time. It is the responsibility of the owner to provide the necessary maintenance for the unit. If a system failure occurs due to improper maintenance during the warranty period, Acson will not be liable for costs incurred to return the unit to satisfactory operation.
Page 54
BELT TENSIONING Table 8: Deflection for Different Pulleys & Belts Sizes (Fix Type) C-C Distance (mm) Deflection (mm) Table 9: Force for Different Pulleys & Belts Sizes (Fix Type) Setting Force to Deflect Belt 15mm per Meter of Span 1.3 x Basic Setting Force (kgf) Belt Section Small Pulley Datum Diameter (mm)
Page 55
PERIODIC MAINTENANCE – YEARLY Entire Unit Inspection In addition to the checks listed in this section, periodic overall inspections of the unit should be accomplished to ensure proper equipment operation. Items such as loose hardware, component operation, refrigerant leaks, unusual noises, etc.
9.0 TROUBLE SHOOTING PROBLEM POSSIBLE CAUSE ACTION 1. Faulty compressor or lack of 1. Check discharge pressure for compression. compression. Inspect compressor and replace if necessary. 2. Temperature of air entering evaporator 2. Reduce load to design KW value. too high. 3.
10.0 ERROR CODE DISPLAY Backlight colour will turn to red when there is any system failure. EER light will turn on and error display section will show the relevant error code as follow: Error code Remarks Not available Indoor fan 1 or 2 overload relay tripped [manual reset] Flow switch failure [manual reset] Water pump failure [manual reset] Comp 1 high pressure or overload relay tripped [manual reset]...
Page 58
ACSON MALAYSIA SALES & SERVICE SDN. BHD. a member of DAIKIN group Business registration No. 198401017130 (129688-D) Lot 4, Lorong 19/1A, Seksyen 19, 46300 Petaling Jaya, Selangor Darul Ehsan, Malaysia. Te: +603 7964 8200 Sales Fax: +603 7956 9900 Service Fax: +603 7956 9907 Acson Careline: 1300 22 3344 www.acson.com.my Johor...