Register Communication; Fig. 20 Register Mode Control Byte - Beckhoff KL3001 Documentation

Single- and dual-channel analog input terminals
Table of Contents

Advertisement

Access from the user program
5.5.2

Register communication

Register access via process data exchange
• Bit 7=1: Register mode
If bit 7 of the control byte is set, the first two bytes of the user data are not used for process data
exchange but written into the register set of the terminal or read from it.
• Bit 6=0: read, bit 6=1: write
Bit 6 of the control bytes is used to specify whether a register should be read or written.
◦ Bit 6=0: a register is read without changing it. The value can be found in the input process image.
◦ Bit 6=1: the user data are written to a register. The process is complete once the status byte in the
input process image has returned an acknowledgment (see example).
• Bit 0 to 5: Address
The address of the register to be addressed is entered in bits 0 to 5 of the control byte.
Control byte in register mode (REG=1)
MSB
REG=1
W/R
REG = 0
: Process data exchange
bin
REG = 1
: Access to register structure
bin
W/R = 0
: Read register
bin
W/R = 1
: Write register
bin
A5..A0 = register address
Addresses A5...A0 can be used to address a total of 64 registers.
Fig. 20: Register mode control byte
The control or status byte occupies the lowest address of a logical channel. The corresponding register
values are located in the following 2 data bytes. (The BK2000 is an exception: here, an unused data byte is
inserted after the control or status byte, and the register value is therefore placed on a word boundary).
Example 1:
Reading of register 8 in the BK2000 with a KL3002 and the end terminal:
If the following bytes are transferred from the control to the terminal,
40
A5
A4
Version: 4.2
A3
A2
A1
A0
KL3001, KL3002