Connection And Led Description; Fig. 12 Kl3001, Kl3002 - Connection And Leds - Beckhoff KL3001 Documentation

Single- and dual-channel analog input terminals
Table of Contents

Advertisement

Mounting and wiring
3.5

Connection and LED description

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
Fig. 12: KL3001, KL3002 – Connection and LEDs
Connection of KL3001
Terminal point
No.
Comment
+Input 1
1
+ Input 1
-Input 1
2
- Input 1
GND
3
Internal ground (internally connected to terminal point 7)
Shield
4
PE contact (internally connected to terminal point 8)
n.c.
5
not used
n.c.
6
not used
GND
7
Internal ground (internally connected to terminal point 3)
Shield
8
PE contact (internally connected to terminal point 4)
Connection of KL3002
Terminal point
No.
Comment
+Input 1
1
+ Input 1
-Input 1
2
- Input 1
GND
3
Internal ground (internally connected to terminal point 7)
Shield
4
PE contact (internally connected to terminal point 8)
+Input 2
5
+ Input 2
-Input 2
6
- Input 2
GND
7
Internal ground (internally connected to terminal point 3)
Shield
8
PE contact (internally connected to terminal point 4)
22
WARNING
Version: 4.2
KL3001, KL3002