Technical Data; Basic Function Principles - Beckhoff KL3001 Documentation

Single- and dual-channel analog input terminals
Table of Contents

Advertisement

2.2

Technical data

Technical Data
Number of inputs
Power supply for the electronics
Signal voltage
Technology
Internal resistance
Common-mode voltage U
Resolution
Conversion time
Measuring error (total measuring
range)
Electrical isolation
Current consumption from the K-bus
Bit width in the K-bus I/O
Configuration
Weight
Dimensions (W x H x D)
Mounting [} 13]
Permissible ambient temperature
range during operation
Permissible ambient temperature
range during storage
Permissible relative air humidity
Vibration / shock resistance
EMC immunity / emission
Protection class
Installation position
Approval
2.3

Basic function principles

The analog input terminals KL3001 and KL3002 process signals in the range between -10 V and +10 V with
a resolution of 12 bits (4095 increments). The terminal inputs are differential inputs with common ground.
Due to the differential inputs, the terminals are particularly suitable for measuring earth free voltage drops.
Cross-currents caused by voltage differences at the input terminals do not lead to any appreciable
measurement distortion up to a difference in potential of 35 V (U
The green Run LEDs indicate the operating state of the associated terminal channel.
• On: Normal operation
• Off: Watchdog-timer overflow has occurred. If no process data are transmitted by the Bus Coupler for
100 ms, the green LEDs go out.
Process data output format
In the delivery state the process data are shown in two's complement form (integer -1 corresponds to
0xFFFF). Other presentation types can be selected via the feature register (R32) [} 37] (e.g. signed amount
representation, Siemens output format).
KL3001, KL3002
KL3001
1
via the K-Bus
-10 V to +10 V
Differential input
> 200 kΩ
35 V max.
CM
12 bits (11 bits for the range between 0 V and 10 V)
~ 1 ms
< ±0.3 % of the full scale value
500 V (K-Bus / signal voltage)
typically 65 mA
Input: 1 x 16 bits of data (1 x 8 bit
control/status optional)
No address or configuration settings
approx. 70 g
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
0 °C ... + 55°C
-25°C ... + 85°C
95%, no condensation
conforms to EN 60068-2-6 / EN 60068-2-27, see also Installation
instructions for enhanced mechanical load capacity [} 17]
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus, ATEX [} 23]
Version: 4.2
KL3002
2
~ 2 ms
< ± 0.30 % (at 0 °C to +55 °C)
< ± 0.75 % (when the extended
temperature range is used)
Input: 2 x 16 bits of data (2 x 8 bit
control/status optional)
-25°C ... +60°C (extended
temperature range)
-40°C ... +85°C
CE, cULus, ATEX [} 24]
= 35 V).
CM
Product Overview
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kl3002

Table of Contents