Mantel Surrounds

Minimum Clearances
If the setting incorporates a mantel the minimum vertical and maximum
horizontal dimensions to combustible mantel identified in the image
below must be followed.
Finishing clearances to COMBUSTIBLES
12.7mm [0.5''] FR Sheetrock
12.7mm [0.5'']
Non-combustible board
152.4mm [6''] Tall
12.7mm [0.5''] FR Sheetrock
Minimum vertical and maximum horizontal dimensions of
combustible mantel.
Finishing and clearances to NON-COMBUSTIBLES
12.7mm [0.5''] FR Sheetrock
12.7mm [0.5'']
Non-combustible board
152.4mm [6''] Tall
12.7mm [0.5''] FR Sheetrock
Minimum vertical and maximum horizontal dimensions of
non-combustible mantel.
Warning! Risk of Fire! Comply with all minimum clearances
to combustibles as specified. Framing or finishing material
closer than the minimum listed must be constructed entirely
of non-combustible materials.
Ceiling
381mm [15''] MAX
914.4mm [36'' ]
330mm [13''] MIN
Measurement is taken
from the top edge of the
Burner level surface
50.8mm [2'' ] MIN
Any construction made
of combustible materials
must be minimum 2"(50.8mm)
below burner level surface.
Ceiling
381mm [15''] MAX
914.4mm [36'' ]
330mm [13''] MIN
Measurement is taken
from the top edge of the
Burner level surface
Any construction made of
non-combustible materials
may be ush with the
burner level surface
Decorative Box
Infill Plate
For appliances with a decorative side box, an infill plate is provided to lift
the material to align with the bottom edge of the appliance. Decorative
boxes must only be used to hold non-combustible accessories/materials.
12.7mm [0.5''] FR Sheetrock
12.7mm [0.5'']
Non-combustible board
152.4mm [6''] Tall
12.7mm [0.5''] FR Sheetrock
Decorative Steel Logs are available as an optional accessory. Please
contact customerservice@ecosmartfire.com
*Decorative logs must NOT be placed directly over an open flame. They
are designed to sit near heat but not over flames.
© Copyright 2004 - 2020 MAD Design Group. All rights reserved. V1119
Ceiling
381mm [15''] MAX
914.4mm [36''
330mm [13''] MIN
Measurement is taken
from the top edge of the
Burner level surface
Any construction made of
non-combustible materials
may be ush with the
burner level surface

Advertisement

Table of Contents
loading

This manual is also suitable for:

Flex single sidedFlex left cornerFlex right cornerFlex bayFlex double sidedFlex peninsula ... Show all

Table of Contents