The FT Series Heating Only, Boiler
Natural Gas Pipe Sizing (Maximum)
Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of 0.5psi or less
and a pressure drop of 0.5 Inch water column. (Based of a 0.60 Specific gravity gas)
For reference only. Referenced from gas pipe manufacturer specifications for actual delivery capacity. The
DOE standard for Natural Gas is 1100 BTU/ft
Pipe
size
10
1/2˝
82
3/4˝
192
383
1-1/4˝
639
1-1/2˝
1260
2930
Table 10. Length of Corrugated Stainless Steel Pipe.
Pipe
size
10
1/2˝
172
3/4˝
360
678
1-1/4˝
1390
1-1/2˝
2090
4020
Table 11. Length of Black Iron Pipe (Schedule 40 Metallic)
. Contact the local gas supplier for actual BTU/ft
3
20
30
40
58
47
41
137
112
97
269
218
188
456
374
325
888
723
625
2080
1700
1470
20
30
40
118
95
81
247
199
170
466
374
320
957
768
657
1430
1150
985
2760
2220
1900
Length (ft)
50
60
80
37
37
29
87
80
69
168
153
132
292
267
232
559
509
440
1320
1200
1040
(Refer to the ANSI Z223.1 NATIONAL
Length (ft)
50
60
80
72
65
56
151
137
117
284
257
220
583
528
452
873
791
677
1680
1520
1300
(Refer to the ANSI Z223.1 NATIONAL
rating.
3
100
150
200
26
20
18
62
48
44
118
91
82
208
171
148
393
320
277
933
762
661
FUEL GAS CODE 2012 EDITION)
100
150
200
50
40
34
104
83
71
195
157
134
400
322
275
600
482
412
1160
928
794
FUEL GAS CODE 2012 EDITION)