Group Name - Mitsubishi Electric AT-50B Installation Manual

Air-conditioner control system advanced touch controller
Hide thumbs Also See for AT-50B:
Table of Contents

Advertisement

Group name

1) Touch the group name input button (labeled 1 in the figure), and enter the
group name in the screen. (up to 16 characters maximum)
2) The name of a group can be copied and pasted into another group name field.
Access the name of the group to be copied using the arrow buttons, and
touch the Copy button [
Access the page to paste the copied group name onto, and touch the Paste
button [
].
Group settings for air conditioning units and Air To Water (PWFY)
units
1) Touch the model selection button (labeled 2 in the figure) to access the Model
selection screen. Touch the model selection button (labeled 6 in the figure) so
that "Air conditioners", "LOSSNAY", or "Air To Water" appears on the screen.
2) Touch the unit selection button (labeled 3 in the figure). On the popup window
that appears, check the address of the units to be included.
3) To assign a remote controller to a group, check the address of controller on the
popup window that appears when the remote controller selection button
(labeled 4 in the figure) is touched.
* Up to two remote controllers can be assigned to each group. (Group settings do not need to
be made for the MA remote controllers.)
* Do not assign a remote controller that does not support Air To Water (PWFY) to Air To
Water (PWFY) group, which may result in unit malfunction.
4) To assign a system controller to a group, check the address of the controller on
the popup window that appears when the system controller selection button
(labeled 5 in the figure) is touched.
* Up to four remote and system controllers combined can be assigned to each group.
* Do not assign a system controller that does not support Air To Water (PWFY) to Air To
Water (PWFY) group, which may result in unit malfunction.
5) After all the settings have been made, touch the Save button.
Group settings for general equipment
1) Touch the model selection button (labeled 2 in the figure) to access the Model selection screen.
Touch the model selection button (labeled 4 in the figure) a few times so that "General Equipment" appears.
2) To change the icons, touch the icon selection button (labeled 7 in the figure), and select the desired one.
3) Touch the general equipment operation setting button (labeled 5 in the figure) to allow or disallow (monitor only) the user to
start/stop the connected equipment via the AT-50B.
In batch and on individual group
On individual group
No operations (Monitor only)
4) Touch the general equipment display setting button (labeled 6 in the figure) and choose between the following ON/OFF status
display options on the HOME screen: "Output status to the general equipment" or "Input status from the general equipment."
5) Touch the unit selection button (labeled 3 in the figure). On the popup window that appears, check the address and the contact
number of the DIDO controller (PAC-YG66DCA) to which the general equipment is connected.
6) After all the settings have been made, touch the Save button on the Groups screen.
1
2
3
Group setting screen
].
Units can be turned on or off either collectively or by group from the AT-50B.
Only certain groups of units can be turned on or off from the AT-50B.
Units cannot be turned on or off from the AT-50B.