Worcester 12/14 Installation And Servicing Instructions page 4

Conventional flue and room sealed bf; floor standing oil-fired pressure jet appliances
Table of Contents

Advertisement

Fig. 1. Cabinet and Pipework Dimensions
92mm
1
2
1. Central heating flow (22mm compression).
3. Gravity feed flow/optional air vent point (1" BSP). 4. Pressure relief discharge pipe (15mm compression).
12/14 Table 2. Electro Oil Inter B9A Burner (See Fig. 21)
Fuel
Nozzle
28 Sec. Kerosene
0.40 60°ES
28 Sec. Kerosene
0.50 60°ES
15/19 Table 3. Electro Oil Inter B9B Burner (See Fig. 22)
Fuel
Nozzle
28 Sec. Kerosene
0.50 60°ES
28 Sec. Kerosene
0.55 80°EH
28 Sec. Kerosene
0.60 60°ES
35 Sec. Gas Oil*
0.50 80°S
20/25 Table 4. Electro Oil Inter B11C Burner (See Fig. 23)
Fuel
Nozzle
28 Sec. Kerosene
0.60 80°EH
28 Sec. Kerosene
0.75 80°EH
28 Sec. Kerosene
0.75 80°EH
35 Sec. Gas Oil*
0.60 80°S
35 Sec. Gas Oil*
0.60 80°S
* NOTE: For use on conventional flue only.
** NOTE: The flue gas temperature is measured in the gas sampling hole on the flue outlet plate. The probe should be inserted to a depth of 50mm and angled towards the flue outlet.
The temperature measured is not an absolute flue gas temperature and is for general guidance purposes only!
NOTE: The pump pressure given is for general guidance only as variations in nozzle output can be up to ± 15%. It is, therefore, essential that the air is adjusted to give the correct CO
NOTE: The nozzle type used on 28 Sec. Kerosene outputs are nozzles calibrated specifically for use with 28 Sec. Kerosene which gives less variation in nozzle output than the standard 35
Sec. Gas Oil nozzles. However, if a 28 Sec. Kerosene nozzle is not available at servicing or commissioning it is appropriate to install a 35 Sec. Gas Oil nozzle providing the output, spray
angle and pattern of the nozzle is the same as the 28 Sec. Kerosene nozzle (e.g. 0.75 80°EH may be replaced with a 0.75.80°H).
Flue Center
1
2. Central heating return (1" BSP).
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
130
1.11
1.41
100
1.30
1.64
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
110
1.40
1.77
115
1.59
2.01
105
1.78
2.25
155
1.80
2.12
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
Pump
Fuel Flow
Pressure
Rate
(p.s.i.)
Kg/h
l/h
130
1.87
2.37
105
2.10
2.66
130
2.34
2.96
120
2.13
2.51
150
2.37
2.79
370 mm
4
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
180
10.0
6.0
195
11.5
7.0
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
215
10.5
8.5
225
10.5
8.75
235
11.5
9.0
235
11.5
9.0
Flue Gas
Approx.
%CO
Temp.
Air
2
(°C)**
Setting
190
11.0-11.5
5.5
205
11.5-12.0
6.0
220
12.0-12.5
6.5
205
11.5-12.0
6.0
220
12.0-12.5
6.5
4
600 mm
4
3
2
Appliance
Input
Output
kW
Btu/hr
kW
13.5
46,000
12
15.5
53,000
14
Appliance
Input
Output
kW
Btu/hr
kW
17
58,000
15
19
65,000
17
21.5
73,000
19
21.5
73,000
19
Appliance
Input
Output
kW
Btu/hr
kW
22.5
77,000
20
25
86,000
22.5
28
96,000
25
25
86,000
22.5
28
96,000
25
Btu/hr
41,000
48,000
Btu/hr
51,000
58,000
65,000
65,000
Btu/hr
68,000
77,000
85,000
77,000
85,000
value.