Floor standing oil fired condensing boiler conventional flue & room sealed flue for fully pumped open vent or sealed central heating systems and domestic hot water cylinders (20 pages)
External oil fired condensing boiler
using balanced flue system
for fully pumped open vent or sealed central heating systems and
domestic hot water water cylinders (20 pages)
Page 1
GREENSTAR DANESMOOR WALL MOUNTED 12/18 & 18/25 WALL MOUNTED OIL FIRED CONDENSING BOILER CONVENTIONAL FLUE & ROOM SEALED FLUE FOR FULLY PUMPED OPEN VENT OR SEALED CENTRAL HEATING SYSTEMS AND DOMESTIC HOT WATER CYLINDERS THE APPLIANCE IS FOR USE WITH KEROSENE (28 SECOND THE APPLIANCE IS FOR USE WITH KEROSENE (28 SECOND OIL) ONLY OIL) ONLY...
Page 2
Wear protective clothing and gloves to Warranty Return Envelope.............................. 1 protect from any sharp edges. Guarantee Registration Card............................1 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 INSTALLATION & 8 718 681 134a (08.08) SERVICING INSTRUCTIONS...
FAULT FINDING - HEATING & HOT WATER FAULT FINDING - BOILER FUNCTION DIAGNOSTICS FOR MO535 RDB CONTROL BOX MO535 RDB CONTROL BOX OPERATION COMBUSTION RECORD SERVICE INTERVAL RECORD INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 CONTENTS 8 718 681 134a (08.08)
OFTEC Standards. Where no specific instruction is given, reference should be made to the relevant codes of practice. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 SAFETY PRECAUTIONS 8 718 681 134a (08.08) & INSTALLATION REGULATIONS...
Drain and thoroughly flush the system to remove the flushing agent and any debris. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 CLEANING 8 718 681 134a (08.08) PRIMARY SYSTEMS...
• Any system connected to the boiler must not have a separate electrical supply. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 MAINS SUPPLY 8 718 681 134a (08.08)
The table and illustration above is a guide only and does not in any way override the de- as the sole fire protection device. aerator manufacturers instructions. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 OIL SUPPLY 8 718 681 134a (08.08)
• A pressure gauge (G), 3 bar minimum, must be fitted to the heating flow pipe. • An automatic air vent (N) must be fitted. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 WATER SYSTEMS & 8 718 681 134a (08.08)
Heating return Auto air vent Non return 1000mm above valve the highest point of the system Stop cock Fill Point INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 WATER SYSTEMS & 8 718 681 134a (08.08) PIPEWORK...
• Pipe (A) should be finished with a partial bend, near the outlet to face the external wall (as shown) to help prevent freezing. Drain pipe. Outside wall. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 PRESSURE RELIEF PIPEWORK 8 718 681 134a (08.08)
* Due to changes in BS 5410 and modern 18/25 building design, these figures no longer incorporate the adventitious ventilation allowance. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 BOILER LOCATION & 8 718 681 134a (08.08) CLEARANCES...
8. Where protection is provided for plastic components, such as guttering, it is essential that this is to the standard specified by the manufacturer of the plastic components. Flat roof boundary Pitched roof C, D boundary INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 FLUE TERMINAL 8 718 681 134a (08.08) POSITIONS...
A - Boiler B - Flue C - Max. 2 bends at 135° D - Anti down-draught terminal E - Chimney INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 CONVENTIONAL FLUE 8 718 681 134a (08.08)
The unpacking of the appliance requires the removal of the board support at the base of the boiler. Instructions for this are on the following pages. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 UNPACKING THE BOILER 8 718 681 134a (08.08)
Page 21
Undo the nut (F) securing the burner and remove the burner (G) from the appliance. Make sure the burner lead is unpluged from the boiler conrol box. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 UNPACKING THE BOILER 8 718 681 134a (08.08)
Page 22
It is important to keep these nuts as they will be required to re-mount the boiler onto the frame. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 UNPACKING THE BOILER 8 718 681 134a (08.08)
Page 23
Note: If a rear exit flue is also used the pipes whilst in the upright position will have to be shortened to miss the flue. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 UNPACKING THE BOILER 8 718 681 134a (08.08)
CAUTION: Ensure t here are no pipes , electrical cables, damp proof courses or other hazards before drilling. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 PIPEWORK POSITIONS & 8 718 681 134a (08.08) FLUE OPENING...
Fit the oil isolation valve (supplied in the accessories box), and return bulkhead fitting to the bracket. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 BOILER INSTALLATION 8 718 681 134a (08.08)
18/25 Plan sectional view Plan sectional view IMPORTANT when refitting the combustion chamber access door Combustion chamber access door tightening sequence. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 COMBUSTION 8 718 681 134a (08.08) CHAMBER...
( J ) and return (K) pipes on the wall bracket. These are push fit connections secured with spring clips (L). INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 CONDENSATE TRAP 8 718 681 134a (08.08)
Fit a return plug (4) (not supplied) to the oil pump and tighten to secure. (on 12/18 model only) Brass air deflector washer Locating circlip INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 OIL BURNER & PUMP 8 718 681 134a (08.08)
Page 33
(G). Connect terminal 6 on the boiler terminal block (G) to the ‘HOT WATER OFF’ at the remote junction box (O). INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 ELECTRICS 8 718 681 134a (08.08)
Page 34
Note: The power indicator on the boiler will function as a demand indicator when the OUTSIDE BOILER programmer is wired into the remote wiring centre. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 ELECTRICS 8 718 681 134a (08.08)
Page 35
Connect the plug from programmer (P) into connector (F). INSIDE BOILER OUTSIDE BOILER Brown Grey Blue Yellow/Green Orange Brown Blue Grey Blue Yellow / Green Orange Brown Blue INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 ELECTRICS 8 718 681 134a (08.08)
Page 36
Move the orange wire from terminal 9 to terminal 6. INSIDE BOILER OUTSIDE BOILER Brown Blue Yellow/Green Blue White Orange Grey Blue INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 ELECTRICS 8 718 681 134a (08.08)
Complete the installation part of the Guarantee Registration Card, and complete a CD10 or equivalent to inform the LABC of the installation. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 PRE-COMMISSIONING 8 718 681 134a (08.08) CHECKS - APPLIANCE...
The (A) in use and (B) must be bled. Bleed air from the primary heat exchanger air vent (B). INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 FILLING THE SYSTEM 8 718 681 134a (08.08)
BURNER LOCKOUT RESET BUTTON ( I ) kerosene and refit. The internal filter is accessed by removing the oil pump cover. Safely dispose of the container/discharge. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 STARTING THE 8 718 681 134a (08.08) APPLIANCE...
The burner and circulating pump should be off. 3 Check that any other controls that are fitted to the system are operating properly. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 STARTING THE 8 718 681 134a (08.08)
The PRV is a safety device and must be checked for correct operation. The expansion vessel pressure must also be checked and adjusted if required. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 INSPECTION AND 8 718 681 134a (08.08) SERVICE...
Page 45
Brass air deflection washer Locating circlip G - Retaining screws - cover H - Cover - oil pump INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 INSPECTION AND 8 718 681 134a (08.08) SERVICE...
Page 46
A fire valve sensor clip is provided for this purpose. Combustion chamber access door tightening sequence. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 INSPECTION AND 8 718 681 134a (08.08) SERVICE...
2 for 12/18 models, fitted into tubes 2 & 3. Remove and fit through baffle access door. COMBUSTION CHAMBER ACCESS DOOR INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 INSPECTION AND 8 718 681 134a (08.08)
Page 48
RESTRICTOR PLATE 1 for 18/25 models, fitted into tube 2. Remove and fit through baffle access door. COMBUSTION CHAMBER ACCESS DOOR INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 INSPECTION AND 8 718 681 134a (08.08) SERVICE...
Part Number: 8 716 156 670 0 0.75 80° ES (25kW output) Part Number: 8 716 109 387 0 INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 SHORT PARTS LIST 18/25 8 718 681 134a (08.08)
Page 52
FAULT FINDING & DIAGRAMS Start BOILER LOCKOUT: Burner not operating normally. Find symptom list below. Indicated by the illumination of the lockout indicator on the fascia. To reset, wait 2 minutes then press the lockout reset button. Are the combustion Are the electrical Check the photocell using the Intermittent...
Start UNDER NO No heating/hot water CIRCUMSTANCES MUST AN APPLIANCE BE LEFT OPERATING WITH ANY CONTROL LINKED OUT OR OVER RIDDEN. Check the power switch and its wiring. Press in the power button Rectify the fault. Is there 230V on terminal Follow the control box Is the power light Is the burner lockout...
FAULT FINDING & DIAGRAMS Start UNDER NO Boiler not operating normally. CIRCUMSTANCES MUST Find symptom list below. AN APPLIANCE BE LEFT OPERATING WITH ANY CONTROL LINKED OUT OR OVER RIDDEN. Is there an automatic bypass fitted, Is the control thermostat Boiler Is the system water Is flow temperature...
Replace Replace Boiler not control box nozzle operating with a MEASURE ALL 230V heating / TESTS BETWEEN hot water NEUTRAL (N) AND THE demand Replace Pipe to Reset Eectrodes & Replace Unblock or Reset air PIN, WIRE OR TERMINAL electrodes/ nozzle combustion leads OK?
Whilst every effort has been taken to ensure the information given is CONTROL BOX OPERATION correct and complete we cannot guarantee that every eventuality has been covered. Worcester, Bosch Group cannot be held responsible for costs incurred by persons not deemed to be competent. STATUS...
Service Provider. Before completing the appropriate Service Interval Record overleaf, please ensure you have carried out the service as described in this manual. Always use Worcester, Bosch Group specified spare parts when replacing all controls. INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR DANESMOOR WALL MOUNTED OIL 12/18-18/25 OIL BOILER 8 718 681 134a (08.08)
Page 58
SERVICE 2 SERVICE 1 DATE DATE ENGINEER NAME ENGINEER NAME COMPANY NAME COMPANY NAME TEL No. TEL No. OFTEC REG No. OFTEC REG No. PUMP PRESSURE: PUMP PRESSURE: NOZZLE CHANGED? NOZZLE CHANGED? F.G.T. °C FLUE PRESSURE: F.G.T. °C FLUE PRESSURE: COMMENTS COMMENTS SIGNATURE...
Page 60
EXCELLENCE COMES AS STANDARD Worcester, Bosch Group Cotswold Way, Warndon, Worcester WR4 9SW. Tel. 01905 754624 Fax. 01905 754619 Worcester, Bosch Group is a trading name of Bosch Thermotechnology Ltd. www.worcester-bosch.co.uk 8 718 681 134a (08.08)