5. SYSTEM PARAMETERS
Parameter
Function
P139
Peak output current detect
P140
Most recent fault code
P141
Most recent fault code -1
P142
Most recent fault code -2
P143
Most recent fault code -3
P201
Closed loop mode
P202 • • • •
P gain (%)
P203 • • • •
I gain (%)
P205 • • • •
Sample interval (x 25 ms)
P206 • • • •
Transducer filtering
P207 • • • •
Integral capture range (%)
P208
Transducer type
P210
Transducer reading (%)
P211 • • • •
0% setpoint
P212 • • • •
100% setpoint
P220
PI frequency cut-off
P700
P701 • • • •
P702
P880
P900 to
(Other than those listed below)
P970
© Siemens plc 1999
Range
Description / Notes
[Default]
0.0 - 99.9
Stores the peak current seen by the motor. Can be reset using ∆ and
[-]
∇buttons.
0 - 9999
Read only. The last recorded fault code (see section 6) is stored in this
[-]
parameter. The stored value can be cleared by using the ∇ button .
Or by resetting to factory defaults (P944)
This is a copy of the code stored in P930.
0 - 9999
This parameter stores the last recorded fault code prior to that stored
[-]
in P140/P930.
0 - 9999
This parameter stores the last recorded fault code prior to that stored
[-]
in P141.
0 - 9999
This parameter stores the last recorded fault code prior to that stored
[-]
in P142.
0 - 2
0 = Normal operation (closed loop control disabled).
[0]
1 = Not used.
2 = Closed loop control using analogue input for transducer feedback
input.
0.0 - 999.9
Proportional gain.
[1.0]
0.00 -
Integral gain.
99.99
0.01% corresponds to the longest integral action time.
[0.00]
1 - 2400
Sampling interval of feedback sensor. The integral response rate is
[1]
slowed down by this factor
0 - 255
0 =
Filter off.
[0]
1 - 255 = Low pass filtering applied to sensor.
0 - 100
Percentage error above which integral term is reset to zero.
[100]
0 - 1
0 = An increase in motor speed causes an increase in sensor
[0]
voltage/current output.
1 = An increase in motor speed causes a decrease in sensor
voltage/current output.
0.0 - 100.0
Read only. Value is a percentage of full scale of the selected input.
[-]
0.00-
Value of P210 to be maintained for 0% setpoint.
100.00
[0.00]
0.00-
Value of P210 to be maintained for 100% setpoint.
100.00
[100.00]
0 - 1
0 = Normal operation
[0]
1 = Switch off inverter output at or below minimum frequency.
Note: Active in all modes.
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further details.
Access only possible with P099 = 1
Specific to PROFIBUS-DP and CANbus operation. See PROFIBUS
or CANbus Handbook for further details.
Access only possible with P099 = 1 or 2
37
English
G85139-H1750-U049-C1
19/08/99