(24) "dC" Capacity DIP switch setting error
Error display: wired controller of IDU and the dash receiver of IDU will display
Error judgment condition and method:
If capacity DIP switch is set to the wrong position, report the error.
Possible reason:
1)
Capacity DIP switch is set to the wrong position.
2)
Detecting circuit is abnormal.
(25) "db" Project debugging
Error display: ODU mainboard, IDU displays
Error judgment condition and method:This is a status code of project debugging, not a error code.
When IDU or ODU displays this code, it means the unit is under debugging status and the IDU cannot be
operated.
Troubleshooting: ——
Possible reason:——
(26) "E1" high pressure protection
Error display: ODU mainboard, IDU displays
Applicable model: all models.
Error judgment condition and method:Judge through detecting the real-time high pressure or
the high pressure switch. If the sensor detects that the high pressure value is over 65°C or the high
pressure switch is disconnected, then it is judged as high pressure, the system will stop the unit for
protection.
Possible reason:
1)
Cut-off valve of ODU is not opened;
2)
High pressure switch operation is abnormal;
3)
Outdoor or indoor fan is abnormal;
4)
Filter screen of IDU or air duct is blocked (heating mode);
5)
Ambient operation temperature is too high;
6)
Refrigerant charging of the system is too much;
7)
System pipeline is blocked;