Fixed Cycle Timing – Level 2 Controller - Gardner Denver DGH Series Instruction Manual

Pressure-swing desiccant type compressed air dryers
Hide thumbs Also See for DGH Series:
Table of Contents

Advertisement

The left tower regenerating light is blinking to indicate the
thermistor location (lower left) that corresponds to the
temperature display.
Press S to advance to screen 8.
7.11.8 Test Mode Screen 8 – Step 8
TEST MODE STEP 8
XX°C XXX°F
The right tower drying light is blinking to indicate the
thermistor location (upper right) that corresponds to the
temperature display.
Caution: Do not advance to step 1 until the left tower
has fully pressurized.
Press S to advance to screen 1.
7.11.9 Test Mode Screen 9 – Attempting to exit test mode
from step 2, 3, or 4
TO EXIT TEST
GO TO STEP 5
Dryer MOP
ISO Class
Dew Point
Cycle Time (minutes)
Time
t0
t1
t2
t3
t4
t5
t6
t7
t8
Purge time (min:sec)
[(t3-t2) or (t7-t6)]
Repress. time (min:sec)
[(t4-t3) or (t8-t7)]
NOTE: When operated in the Demand Mode, drying times t4-t0 and t8-t4 can extend to a maximum of 30 minutes each. Purge times in the
Demand Mode, regardless of the ISO Class selection, will always be equal to the purge times of the ISO Class 2 (10 min.) Fixed Cycle (3:54
for 150 psig MOP and 2:54 for 250 psig MOP).
60-150 psig
1
2
-73°C
-40°C
-20°C
-100°F
-40°F
-4°F
4
10
Time from start of cycle
(minutes : seconds)
00:00
00:00
00:00
00:02
00:02
00:02
00:06
00:06
00:06
01:12
04:00
06:55
02:00
05:00
08:00
02:02
05:02
08:02
02:06
05:06
08:06
03:12
09:00
14:55
04:00
10:00
16:00
Reference Data
01:06
03:54
06:49
00:48
01:00
01:05
Fixed Cycle Timing – Level 2 Controller
This screen is displayed for 5 seconds if the user attempts
to exit test mode from step 2, 3, or 4.
At the end of the 5-second time period, the display returns
to the previous screen (2, 3, or 4).
7.11.10 Test Mode Screen 10 – Attempting to exit test
mode from step 6, 7, or 8.
TO EXIT TEST
GO TO STEP 1
This screen is displayed for 5 seconds if the user attempts
to exit test mode from step 6, 7, or 8.
At the end of the 5-second time period, the display returns
to the previous screen (6, 7, or 8).
3
4
1
+3°C
-73°C
+38°F
-100°F
16
24
4
00:00
00:00
00:02
00:02
00:06
00:06
10:50
00:48
12:00
02:00
12:02
02:02
12:06
02:06
22:50
02:48
24:00
04:00
10:44
00:42
01:10
01:12
Table 7-4
- 37 –
7. Controller – Level 2
120-250 psig
2
3
-40°C
-20°C
-40°F
-4°F
10
16
Time from start of cycle
(minutes : seconds)
00:00
00:00
00:02
00:02
00:06
00:06
03:00
05:40
05:00
08:00
05:02
08:02
05:06
08:06
08:00
13:40
10:00
16:00
02:54
05:34
02:00
02:20
7. Controller – Level 2
4
+3°C
+38°F
24
00:00
00:02
00:06
09:20
12:00
12:02
12:06
21:20
24:00
09:14
02:40